Insulation Testing Device with 0-10 MΩ Monitoring Range Dual-Bus Monitoring and Hierarchical Alarms for Accurate Fault Detection
Insulation Testing Device
Functional Features
- Monitoring range: 0-10 MΩ (extendable up to 100 MΩ), accuracy ±5%, resolution ≤1 kΩ
- Dual-bus monitoring: Independently measures insulation resistance between positive and negative electrodes to ground
- Supports hierarchical alarms (early warnings and alerts) with customizable thresholds
- Branch circuit inspection: Identifies faulty insulated branches using sampling resistor switching
- Distinguishes between fault types including single-pole grounding and bipolar unbalanced grounding
- Adaptive monitoring mode: Automatically adjusts measurement modes based on system voltage fluctuations
- Supports host, extension, and slave operation modes
- Supports coordinated testing of system interconnection faults between master and slave devices
- Supports main handset mode for split-screen designs
- Compatible with both digital and analog leakage current sensors
- Modular design with parameter import via USB drive
- Flexible configuration: Integrates with DC monitoring devices or standalone human-machine interface
- Automatic switching of bridge resistor values for 110V/220V system adaptation
Technical Specifications
Monitoring Parameters
| Parameter Item |
Typical Value/Range |
Description |
| Insulation resistance measurement range |
0.1kΩ~10MΩ |
High-resistance range for high-voltage systems (photovoltaic, energy storage); low-resistance range for precise alarms |
| Measurement accuracy |
±0.5% (full range) |
High-precision design ensures reliable leakage current warning performance |
| Voltage Monitoring Range |
DC 24V~1500V |
Compatible with wide voltage ranges including communication base stations (48V), substations (220V), and photovoltaic systems (1500V) |
| Resolution |
≤1 kΩ (insulation resistance); ≤0.1 V (bus voltage) |
High resolution enables analysis of subtle insulation degradation trends |
| Response time |
≤5 seconds (system-wide scan) |
Quickly detect insulation degradation with branch localization time ≤30 seconds |
Fault Localization and Performance Parameters
| Parameter Item |
Typical Value/Range |
Description |
| Branch positioning accuracy |
±5% (insulation resistance) |
|
| Fault Type Identification |
Unipolar grounding, bipolar unbalanced grounding, capacitive grounding |
|
| Capacitive Compensation Function |
Supports ground capacitance ≤ 100 μF |
|
Communication and Interface Parameters
| Parameter Item |
Typical Value/Range |
Description |
| Communication Interface |
RS485 |
Supports Modbus RTU protocol |
| Alarm Output |
Dry contact signal (passive contact) |
Always-on/always-off contact, rated capacity 250 V AC/5 A, directly drives relay or audio-visual alarm |
| Data storage |
≥100,000 event records |
Stores historical insulation resistance data and fault events with timestamps; supports export to USB drives |
| SOE resolution |
≤1ms |
Records sequence of fault occurrences for multi-system collaborative analysis |
Electrical and Environmental Adaptability
| Parameter Item |
Typical Value/Range |
Description |
| Working voltage |
DC85V~265V |
Wide voltage input, compatible with 110V/220V DC systems |
| Power |
12V60W |
Supports power supply for up to 720 digital CT units |
| Working temperature |
-40℃~+70℃ |
|
Safety and Reliability Parameters
| Parameter Item |
Typical Value/Range |
Description |
| Isolation Voltage |
≥2500 V AC |
Between input, output, and communication circuits; suppresses transient overvoltages from surges or lightning strikes |
| Surge protection |
8/20 μs surge current: 20 kA (IEC 61000-4-5) |
Prevents equipment damage caused by wiring errors |
| Self-checking function |
Power-on self-test (bridge arm resistance, ADC, communication) |
Ensures long-term equipment reliability |