Rating: Rated voltage:380V. 50-60Hz
Application:
mainly applicable in power stations, power substation, industrial and mining enterprises as an energy converter, distributor, and controller of power, light, and distribution devices.
Rating: Rated voltage: 380V.
50-60Hz
Application:
mainly applicable in power stations, power substations, and industrial and mining enterprises as an energy converter, distributor, and controller of power, light, and distribution devices.
1. Ambient air temperature: -15℃ ~+40℃
Daily average temperature: ≤35℃
When the actual temperature exceeds the range, it should be reduced by the
capacity accordingly.
2. Transport and store temperature: -25℃ ~+55℃. do not exceed +70℃ in short
time.
3. Altitude: ≤2000m
4. Relative humidity: ≤50%, when temperature is +40℃
When the temperature is low, larger relative humidity is allowed. When it is +20℃, the relative humidity can be 90%. Since the temperature change will cause our condensation.
5. Installation inclination: ≤5%
6. Applicable in places without corrosive and flammable gases.
Note: Customized products are available.
1. Main Technical Data Sheet 1
| Type | Rated voltage (V) |
Rated current (A) |
Rated short-circuit breaking current (kA) |
Rated short-circuit withstand current (1s)(1kA) |
Rated peak withstand voltage (kA) |
| GGD1 | 380 | A 1000 | 15 | 15 | 30 |
| 380 | B 600(630) | 15 | 15 | 30 | |
| 380 | C 400 | 15 | 15 | 30 | |
| GGD2 | 380 | A 1500(1600) | 30 | 30 | 63 |
| 380 | B 1000 | 30 | 30 | 63 | |
| 380 | C 600 | 30 | 30 | 63 | |
| GGD3 | 380 | A 3150 | 50 | 50 | 105 |
| 380 | B 2500 | 50 | 50 | 105 | |
| 380 | C 2000 | 50 | 50 | 105 |
2. Main bus
1) Single copper busbar adopted when the rated current<=1500A
2) Double copper busbar adopted when the rated current>1600A.
3) A brushing &anodizing process was adopted, which is better than the traditional zinc-coated process.
3. Selection of horizontal bus Sheet 2
| Rated current (A) |
Copper Busbar specification (mm) |
| 400 | 40×4 |
| 630 | 50×5 |
| 1250 | 60×10 |
| 1600 | 80×10 |
| 2000 | 2×(60×10) |
| 2500 | 2×(80×10) |
| 3150 | 2×(100×10) |
4. Selection of neutral earthgin bus Sheet 3
| Cross-section of phase conductor (mm²) |
Cross-section of PE(N) conductor (mm²) |
| 500~720 | 40×5 |
| 1200 | 60×6 |
| >1200 | 60×10 |
1. The accuracy and quality of the switchgear could be ensured as the framework parts and special parts supplied by DSY. Modular design of the Overall and mounting dimensions(mm) concerning (E=20mm), which has cut production time and enhanced efficiency.
2. The heat dispersion channel at the top and bottom of the switchgear forms a ventilation loop to disperse the heat.
3. Easy for installation and dismantling.
4. The switchgear with a perfect earthing protection system.
5. The cover of the switchgear could be removed for installation and adjustment of the main bus bar. There are also rings for lifting and delivery of switchgear
6. The protection degree is IP30. As per your requirements, switchgears with a protection degree of IP20~IP40 are available.
7. Flexible circuit plans are available.