N2XS(F)H 6/10 (12)kV Cable XLPE Insulation LSZH Sheath 8.7/15 (17.5) KV Cable 12/20 (24)kV Cable
Product Overview
N2XS(F)H cable is longitudinally waterblocking cable and N2XS(FL)H cable is dual longitudinal and radial waterblocking cable. These medium voltage power cables are designed for 10kV, 15kV, 20kV, and 30kV applications and are commonly installed in cable ducts, providing additional mechanical protection. The waterblocking layers prevent water ingress from reaching the insulation layer, ensuring optimal performance even in waterlogged conditions.
Key Specifications
Rated Voltage
6/10kV 8/15kV 12/20kV
Size Range
35-630mm²
Conductor Material
Copper
Insulation Material
XLPE
Working Temperature
-40°C to +90°C
Jacket Material
LSZH
Application
Building
Type
Medium Voltage
Standard
IEC 60502-2, IEC 60228
Warranty
100% Qualified
Cable Characteristics
| Parameter |
6/10 (12)kV |
8.7/15 (17.5)kV |
12/20 (24)kV |
18/30 (36)kV |
| Test Voltage |
21kV AC 50Hz (15 mins) |
30kV AC 50Hz (5 mins) |
42kV AC 50Hz (5 mins) |
63kV AC 50Hz (15 mins) |
| Temperature Rating |
-20°C to +60°C |
| Permissible Conductor Operating Temperature |
+90°C |
| Permissible Short Circuit Temperature (up to 5 sec) |
250°C |
| Minimum Bending Radius |
15 x overall diameter |
Cable Construction
| Component |
N2XS(F)H Cable |
N2XS(FL)H Cable |
| CONDUCTOR |
Class 2 stranded copper |
Class 2 stranded copper |
| INSULATION |
XLPE (Cross-linked Polyethylene) |
XLPE (Cross-linked Polyethylene) |
| SCREEN |
Copper wires and tape |
Copper wires and tape |
| WATER-BLOCKING |
Longitudinal Water-swellable tape either side of the screen |
Layer 1 - Longitudinal Water-swellable tape either side of screen Layer 2 - Radial Waterblocking Al/PET bonded to sheath |
| OUTER SHEATH |
LSZH (Low Smoke Zero Halogen) |
LSZH (Low Smoke Zero Halogen) |
Detailed Cable Specifications
| No. of Cores |
Nominal Cross Sectional Area (mm²) |
Nominal Conductor Diameter (mm) |
Number Wires Conductor (mm) |
Nom. Thickness Semi-con. Layer (mm) |
Nominal Insulation Thickness (mm) |
Minimum Insulation Thickness |
Nominal Diameter Over Insulation (mm) |
| 1 | 35 | 16 | 6.9 | 7 x 2.62 | 0.5 | 0.4 | 5.5 | 4.85 | 19.1 |
| 1 | 50 | 16 | 8.1 | 10 x 2.62 | 0.5 | 0.4 | 5.5 | 4.85 | 20.3 |
| 1 | 70 | 16 | 9.7 | 14 x 2.62 | 0.5 | 0.4 | 5.5 | 4.85 | 21.9 |
| 1 | 95 | 16 | 11.4 | 19 x 2.62 | 0.5 | 0.4 | 5.5 | 4.85 | 23.6 |
| 1 | 120 | 16 | 12.7 | 19 x 2.97 | 0.5 | 0.4 | 5.5 | 4.85 | 24.9 |
| 1 | 150 | 25 | 14.5 | 19 x 3.20 | 0.5 | 0.4 | 5.5 | 4.85 | 26.7 |
| 1 | 185 | 25 | 15.9 | 27 x 2.62 | 0.5 | 0.4 | 5.5 | 4.85 | 28.1 |
| 1 | 240 | 25 | 18.6 | 48 x 2.62 | 0.5 | 0.4 | 5.5 | 4.85 | 30.8 |
| 1 | 300 | 25 | 20.7 | 61 x 2.62 | 0.5 | 0.4 | 5.5 | 4.85 | 32.9 |
| 1 | 400 | 35 | 23.5 | 61 x 2.97 | 0.5 | 0.4 | 5.5 | 4.85 | 35.7 |
| 1 | 500 | 35 | 26.5 | 61 x 3.29 | 0.5 | 0.4 | 5.5 | 4.85 | 38.7 |
| 1 | 630 | 35 | 30.2 | 61 x 3.80 | 0.5 | 0.4 | 5.5 | 4.85 | 42.9 |