This cable consists of one, two, or three conductors of hard aluminum 1350, each individually insulated with black cross-linked polyethylene (XLPE). The conductors are joined together with a neutral conductor of hard aluminum 1350 insulated with white cross-linked polyethylene (XLPE).

| Number of Conductors | Phase Conductor | Neutral Conductor | Approx. Total Weight (kg/100m) | Current-Carrying Capacity* (A) at 75 °C | ||||||
|---|---|---|---|---|---|---|---|---|---|---|
| Size (AWG/kcmil) | Nominal Area (mm²) | Number of Strands | Nominal Insulation Thickness (mm) | Size (AWG/kcmil) | Nominal Area (mm²) | Number of Strands | Nominal Insulation Thickness (mm) | |||
| 1 | 6 | 13.3 | 7 | 1.14 | — | — | — | — | 7 | 60 |
| 1 | 6 | 13.3 | 7 | 1.14 | 13 | 2 | 20 | 3 | 26 | 48 |
| 1 | 4 | 21.2 | 7 | 1.52 | — | — | — | — | 11 | 78 |
| 1 | 4 | 21.2 | 7 | 1.52 | 21 | 2 | 31 | 3 | 41 | 62 |
| 1 | 2 | 33.6 | 7 | 1.52 | — | — | — | — | 15 | 103 |
| 2 | 2 | 33.6 | 7 | 1.52 | 44 | 3 | 58 | — | 82 | — |
| 2 | 4 | 21.2 | 7 | 1.52 | 39 | 3 | 54 | — | 82 | — |
| 1 | 1/0 | 53.5 | 19 | 2.03 | — | — | — | — | 23 | 136 |
| 2 | 2 | 33.6 | 7 | 1.52 | 61 | 3 | 84 | — | 108 | — |
| 1 | 2/0 | 67.4 | 19 | 2.03 | — | — | — | — | 28 | 156 |
| 1 | 3/0 | 85.0 | 19 | 2.03 | — | — | — | — | 34 | 178 |
| 2 | 1/0 | 53.5 | 19 | 2.03 | 92 | 3 | 125 | — | 142 | — |
| 1 | 300 | 152.0 | 37 | 2.41 | — | — | — | — | 57 | 252 |
| 1 | 350 | 177.0 | 37 | 2.41 | — | — | — | — | 65 | 276 |
| 3 | 4/0 | 107 | 19 | 2.03 | 240 | — | 220 | — | — | — |
| 1 | 500 | 253 | 37 | 2.41 | — | — | — | — | 89 | 338 |
Note: Dimensions and weights are subject to manufacturing tolerances. *Current-carrying capacity is based on Table B.310.15(B)(2)(7) for an electrical conduit in NOM-001-SEDE, for an ambient soil temperature of 20 °C, relative humidity of 90%, load factor of 100%, and affected by the number of conductors.