| Description | ||
| Suitable for installation in LPZ 1-2 and subsequent lightning protection zones, suitable for fine lightning protection in single-phase power supply systems. | ||
| Features | ||
| 1.Full mode protection | ||
| 2. Large flow capacity and super low residual pressure | ||
| 3.No leakage current, no afterflow | ||
| Parameter | ||
| Standard | IEC 61643.11 | |
| SPD type | T2,T3 | |
| Models | SLV-40S | SLV-80S |
| Parameter | ||
| Nominal operating voltage Un | 220Vac(50Hz) | |
| Maximum continuous operating voltage Uc | 320Vac(50Hz) | |
| Nominal discharge current (8/20μs)In | 20kA | 40kA |
| Maximum discharge current (8/20μs) Imax | 40kA | 80kA |
| Voltage protection level In@Up | ≤1.25kV | ≤1.8kV |
| L-N,L-E,N-E(3kA&6kV) Uoc | ≤650V | |
| Response time tA | ≤25ns | |
| Protection Circuit | L-N,L-E,N-E | |
| Lightning stroke count | ||
| Counting current range | 0.5kA(8/20μs)-80kA(8/20μs) | |
| Counting digit | 0-999 | |
| Mechanical parameters | ||
| Installation method | 4 fixed holes, DIN Rail 35mm | |
| Screw torque | 5N*m | |
| Strip length | 12mm | |
| Wiring cross-sectional area | 2.5mm^2-10mm^2 | |
| Product size | 150mmx88mmx80mm | 150mmx108mmx80mm |
| Shell material and surface technology | Cold rolled steel plate painted black | |
| Alarm system | ||
| Deterioration indication | LED green: OK; Off: Fail | |
| Remote signaling contact type | Normally closed and normally open switching contacts | |
| Remote signaling contact switching ability | 125 Vac / 1 A, 125 Vdc A / 0.2 | |
| Maximum connection capacity of remote signaling | 2.5mm^2 | |
| Work environment | ||
| Installation position | Indoor | |
| Degrees of protection provided by enclosure | IP20 | |
| Temperature range | -40℃…+80℃ | |
| Humidity range | Relative humidity ≤ 95% (max 40 ℃) | |