Specifications
Brand Name :
LLH
Model Number :
SLV-40T
Place of Origin :
Guangdong Province, China
MOQ :
1 piece
Payment Terms :
L/C,D/A,D/P,T/T,Western Union
Supply Ability :
5000-10000 pieces/month
Delivery Time :
7-15 days
Packaging Details :
Box
Price :
USD$120-USD$190
Nominal Operating Voltage (Un) :
220Vac(50Hz)
Maximum Continuous Operating Voltage (Uc) :
320Vac(50Hz)
Nominal Discharge Current (In) :
20kA/ 40kA
Maximum Discharge Current (Imax) :
40kA/ 80kA
Voltage Protection Level (Up) :
≤1.25kV (L123-N)、≤1.8kV (L123-E)、≤650V (N-E)
Response Time :
≤25ns
Description
Product features
● Full mode protection
● No leakage current, no afterflow
● Large flow capacity and super low residual pressure
● Suitable for installation in LPZ 1-2 and subsequent lightning protection zones, suitable for fine lightning protection devices in three-phase power supply systems.

Product Specification


T2 T3 Lightning Surge Protection Device 3 Phase AC SPD 220V 20kA 40kA

Standards IEC 61643.11
SPD type T2,T3
Models

SLV-40T

SLV-80T

Nominal operating voltage Un 220Vac(50Hz)
Maximum continuous operating voltage Uc 320Vac(50Hz)
Nominal discharge current (8/20μs) In 20kA/40kA
Maximum discharge current (8/20μs) Imax 40kA/80kA
Voltage protection level In@Up ≤1.25kV/≤1.8kV
L123-N,L123-E,N-E(3kA&6kV) Uoc ≤650V
Response time tA ≤25ns
Protection Circuit L1,L2,L3-N,L1,L2,L3-E,N-E
Counting current range 0.5kA(8/20μs)-80kA(8/20μs)
Counting digit 0-999

Mechanical parameters

Installation method 4 fixed holes, DIN Rail 35mm
Screw torque 5N*m
Strip length 12mm
Wiring cross-sectional area 2.5mm²-10mm²
Product size

SLV-40T:178mmx116mmx75mm

SLV-80T:197mmx139mmx90mm

Shell material and surface technology Cold rolled steel plate painted black
Deterioration indication LED green: OK; Off: Fail
Remote signaling contact type Normally closed and normally open switching contacts
Remote signaling contact switching ability 125 Vac / 1 A, 125 Vdc A / 0.2
Maximum connection capacity of remote signaling 2.5mm²
Installation position Indoor
Degrees of protection provided by enclosure IP20
Temperature range -40℃…+80℃
Humidity range Relative humidity ≤ 95% (max 40 ℃)

Notices
1.Install the SPD in LPZ 1-2 or subsequent lightning protection zones, ensuring the distance to protected equipment does not exceed 10 meters.

2.Use wiring with cross-sectional area 2.5mm²-10mm² and tighten screws to 5N·m torque for secure connections.

3.Ensure reliable grounding with a ground resistance ≤4Ω to guarantee surge current diversion efficiency.

4.Replace the SPD immediately if the LED indicator turns off (failed status) or after experiencing a severe surge impact.

5.Do not disassemble the product by yourself; improper operation may damage internal components and cause safety risks.

6.Avoid using the product in environments beyond the specified temperature (-40℃~+80℃) and humidity range

FAQ
Q1: What is the difference between SLV-40T and SLV-80T?

A1: The core difference is nominal discharge current (In) and maximum discharge current (Imax): SLV-40T has In=20kA/Imax=40kA, while SLV-80T has In=40kA/Imax=80kA. Other performance parameters and structural design are consistent.

Q2: Can this SPD be used for single-phase power systems?

A2: No, SLV-40T/SLV-80T is specifically designed for three-phase systems. For single-phase applications, choose SLV-40S/SLV-80S series products.

Q3: What is the function of remote signaling contacts?

A3: The normally closed and normally open switching contacts allow connection to monitoring systems, enabling remote alerts when the SPD fails.

Q4: Does the product require regular maintenance?

A4: Regular visual inspection is recommended (quarterly): check LED status and wiring tightness. No additional maintenance is needed under normal operating conditions.

Q5: Is the SPD compatible with different grounding systems?

A5: Yes, it is compatible with TN, TT, and IT grounding systems, as long as the grounding resistance meets the requirement (≤4Ω).

Send your message to this supplier
Send Now

T2 T3 Lightning Surge Protection Device 3 Phase AC SPD 220V 20kA 40kA

Ask Latest Price
Watch Video
Brand Name :
LLH
Model Number :
SLV-40T
Place of Origin :
Guangdong Province, China
MOQ :
1 piece
Payment Terms :
L/C,D/A,D/P,T/T,Western Union
Supply Ability :
5000-10000 pieces/month
Contact Supplier
video
T2 T3 Lightning Surge Protection Device 3 Phase AC SPD 220V 20kA 40kA
T2 T3 Lightning Surge Protection Device 3 Phase AC SPD 220V 20kA 40kA
T2 T3 Lightning Surge Protection Device 3 Phase AC SPD 220V 20kA 40kA

Shenzhen LLH Electrical Co., Ltd.

Verified Supplier
1 Years
shenzhen
Since 2018
Business Type :
Manufacturer
Total Annual :
1000000-10000000
Employee Number :
20~100
Certification Level :
Verified Supplier
Contact Supplier
Submit Requirement