| Product features |
|
●Made of high-quality QA copper wire wound
|
|
●Adopting a broadband magnetic core to synchronize lightning frequency and prevent magnetic saturation
|
|
●This product is applied in scenarios where the decoupling distance of cables between two levels (T1-T2, T2-T2, T2-T3) of lightning protection devices is insufficient, playing a role in energy coordination between lightning protection devices, preventing damage to subsequent lightning protection devices by lightning current, and reducing residual voltage.
|

| Standards | IEC 61643.21 |
| Models |
LTS-40A LTS-63A |
| Maximum sustainable operating voltage Uc | 250Vac(50Hz) |
| Maximum load current IR max | 40A/63A |
| Inductive reactance Ls | ≥15μH |
| Installation method | DIN Rail 35mm |
| Screw torque | 5N*m |
| Strip length | 12mm |
| Wiring cross-sectional area |
LTS-40A:≥6mm² LTS-63A:≥10mm² |
| Product size | 90mmx36mmx68mm |
| Shell material and flame retardant grade | Mineral nylonPA6,V0 |
| Installation location | Indoor |
| Shell protection rating | IP20 |
| Temperature range | -40℃…+80℃ |
| Humidity range | Relative humidity≤95%(max 40℃) |
●Install the decoupler between two levels of SPDs to ensure sufficient energy coordination.
●Select the model based on the system's maximum load current (40A/63A).
●Use wiring with cross-sectional area ≥6mm² (LTS-40A) or ≥10mm² (LTS-63A) and tighten screws to 5N·m torque.
●Ensure the installation environment meets temperature (-40℃~+80℃) and humidity requirements.
●Avoid installing in environments with strong electromagnetic interference to prevent performance degradation.
●Regularly inspect the product for physical damage or loose connections; replace if faulty.
FAQ
Q1: What is the function of a decoupling device?
A1: It coordinates energy between different levels of SPDs, preventing damage to subsequent SPDs and reducing residual voltage when decoupling distance is insufficient.
Q2: What is the inductive reactance of the product?
A2: The inductive reactance (Ls) is ≥15μH, ensuring effective energy isolation.
Q3: What wiring cross-sectional area is required?
A3: LTS-40A requires ≥6mm² wiring, while LTS-63A requires ≥10mm² wiring.
Q4: Is the product certified?
A4: Yes, it holds TUV and CE certifications, meeting international safety standards.
Q5: Can it be used for DC systems?
A5: No, it is specifically designed for AC 250Vac(50Hz) systems. For DC applications, choose dedicated DC decoupler models.