Power Station Lightning Current Silicon Rubber Material Surge Arresters
Description:
YongDe Surge Arresters can be applied to a variety of systems including substation equipment, AC-DC converters, railway power system and power distribution units ranging from 0.25kV to 765kV systems. Metal oxide type surge arresters offer such special features inherent in the gap-less structure, such as a quick response to surge voltage, high energy dissipation capability, safe operation, compactness / lightweight and freedom from pollution.
Features:
1. Compact and Lightweight
2. Extremely Safe Pressure Relief Performance
3. Superior Performance against Environmental Contamination
4. Directly Molded Structure
5. Compliance with International Standards(IEC60099-4)
6. Simple Support Structure
7. Manufactured at Advanced ISO-9001 certified facilities
Operating condition:
1) Environment temperature: -40--+40 degree
2) altitude: <1000m
3) 48HZ
4) Power frequency voltage should not be more than continuous running voltag
5) Max wind speed should be less than 35m/s
6) Earthquake intensity should be less than 7 degree
7) If used in contamination area, should be noted in advance.
Specifications:
| Type | YH5W5-60/150 |
| Rated voltage---------kV | 60 |
| MOCV ----------------kV | 48 |
| Nominal Current-------kV | 5 |
| Residual voltage of steep impulse----at 5kA(kV) | 163 |
| 8/20µS Residual voltage of lightning impulse current kV(Peak value)-----at 5kA(kV) | 150 |
| Residual voltage of switching impulse current kV (peak value)----at 1kA (kV) | / |
| 1mA D.C reference voltage (kV) | 85 |
| Line discharge level | 1 |
| 2mS long duration impulse current A | 400 |
| 4/10µS High current impulse kA | 100 |
| Lightning impulse withstand kV | 325 |
| Power frequency voltage withstand(dry/wet)kV | 140 |
| 0.1S TOV--------------kV | 72 |
| 1S TOV----------------kV | 69 |
| 10S TOV---------------kV | 66 |
| 1200S TOV-------------kV | 60 |
| Creepage distance ----mm | 2070 |
| Material employed in series non-linear resistor | Zinc Oxide |