RM33-200kVA To 500kVA Modular UPS Power Supply Dual Conversion 50kW Power Module
Description:
3U single power module with power up to 50kW Single 42U cabinet with capacity up to 500KW
Supports power system N+1
Modular design reduces MTTR (mean time to maintenance) High scalability
Built-in maintenance bypass switch for easy maintenance.
Output non-interruptible high-efficiency double conversion online UPS
Flexible battery configuration and adjustable charging current High overload capacity Power supply walk-in function
A+42U-200S (PM-50S), A+42U-300 (PM-50) and A+42U-500 (PM-50) can be equipped with 4 switches
Parameters
| Model | A+ 42U-200S (PM-50S) | A+ 42U-300S (PM-50S) | A+ 42U-300 (PM-50) | A+ 42U-400 (PM-50) | A+ 42U-500 (PM-50) |
| Unit | 3 Phase Input / 3 Phase Output |
| Power Capacity | 200KW | 300KW | 300KW | 400KW | 500KW |
| Battery Type | External Battery |
| Single Battery Capacity | 50KVA/50KW |
| Number of Batteries | 4 | 6 | 6 | 8 | 10 |
| Connection Method (Parallel) | Lower Wire | Upper Wire | Upper Wire | Upper/Lower Wire | Upper/Lower Wire |
| Number of switches | 2 |
| Input |
| Nominal Voltage | 3 x 380/400/415 VAC (3Ph+N) |
| Voltage range | 110-300 VAC @ 50% (Load), 176-276 VAC @ 100% (Load) |
| Nominal Frequency | 50/60 Hz (Auto Detect) |
| Frequency Range | 40Hz - 70Hz |
| Power Factor | 100% (Load) > 0.99, 50% (Load) > 0.98 |
| Total Harmonic Distortion (THD) | < 4% @ 100% Load |
| Output |
| Nominal Voltage | 3 x 380/400/415 VAC (3Ph+N) |
| Voltage Regulation (Stability) | ≤ ±1% (Nominal), ≤ ±2% (Unbalanced Load) |
| Nominal Frequency | 50/60Hz |
| Frequency Range (Synchronization Range) | 46Hz - 54Hz or 56Hz - 64Hz |
| Overload capacity | 1 hour ≤ 110%, 10 minutes for 111% to 125%, 1 minute for 126% to 150%, 200 milliseconds for > 150% |
| Harmonic distortion | ≤2%THD (linear load), ≤4%THD (non-linear load) |
| Efficiency | 95.50% |
| Battery / Charging |
| Nominal Voltage | +/– 192V ~ +/- 240V (Optional) |
| Maximum Voltage | +/- 240V (12V x 40 cells) |
| Minimum Voltage | +/- 192V (12V x 32 cells) |
| Charging Voltage | 2.28V / Cell (2.25V to 2.33V Optional) |
| Equalizing Voltage | 2.35V / Cell |
| Temperature Compensation | Supported |
| Maximum Charging Current (Per Module) | 12A (Adjustable) |
| Dimensions |
| Machine Dimensions (W x D x H) mm | 850 x 600 x 2000 | 850 x 600 x 2000 | 1065 x 600 x 2010 | 1100 x 600 x 2010 | 1065 x 1000 x 2000 |
| Net Weight (kg) | 275 | 282 | 287 | 308 | 420 |
| Operating Environment |
| Operating Temperature | 0-40°C |
| Relative Humidity | 0-95% (Non-condensing) |
| Altitude | < 1000m Standard Altitude |
| IP Protection Level | IP 20 |
| Control Management |
| RS-232 Interface/USB | Supports Windows Series, Linux, and MAC |
| SNMP Card(Optional) | SNMP Card for Network Management |
| Safety Standards |
| Safety | IEC/EN 62040-1 |
| Battery Compatibility | IEC/EN 62040-2 Category C3 |
| Note: The asterisk indicates that the UPS must be used in an environment with an output voltage of 1000m or higher, and the output power must be reduced by 10%. |