The differential air pressure switch is used to control the differential pressure of the air for filters, fans, air ducts, air-conditioning and ventilation systems. This pressure switch is especially suitable for control and safety functions in air-conditioning systems, providing the fan stop signal and dirty filters signal.
| Model | QAD | 
| Media | Air,non-combustible and non-aggressive gasses | 
| Max Operating Pressure | 10kPa | 
| Mounting Position | Diaphragm in any vertical plane | 
| Degree of protection | IP54(with cover) | 
| Operating Temperature | -40℃to 85℃ | 
| Contact Arrangement | SPDT | 
| Electrical Rating | Resistance: Initial: < 50 milliohms; | 
| Current1.5A resistive(0.4A inductive) 250V | |
| Electric Connection | 6.3x0.8 blade 46244 or screw terminals | 
| Material | Housing:ABS | 
| Duct connectors: ABS | |
| Membrane: Silicone | |
| Cable sleeve:PVC | |
| Weight | 0.15kg(0.35kg with flexible pipe) | 
| Connection | φ6.0mm for tube connection | 
| Approval | UL,CE,RoHS | 
QAD series air pressure controls is factory-calibrated for vertical position. If installed horizontally, this will affect the switching point as following:
• with cover facing upwards, switching point is 15Pa higher than scale;
• with cover facing downwards, switching point is 15Pa lower than scale.
Note: Do not install upside down with trip pressures of less than 50pa!
| Model | Pressure Range | Differential | Tolerance | 
| QAD-1 | 20~200Pa | 10Pa | ±15% | 
| QAD-2 | 30~300Pa | 10Pa | ±15% | 
| QAD-3 | 40~400Pa | 20Pa | ±15% | 
| QAD-4 | 50~500Pa | 20Pa | ±15% | 
| QAD-5 | 200~1000Pa | 100Pa | ±15% | 
| QAD-6 | 500~2500Pa | 150Pa | ±15% | 
| QAD-7 | 1000~5000Pa | 250Pa | ±15% |