Busbar Connection Ssytem 200A, 15 kV Class Deadbreak Reducing Tap Plug (RTP) with Bushing Extender
Application
Chuangyin® Reducing Tap Plug is widely applicable for the transition of a 600 A deadbreak system to a 200 A deadbreak or loadbreak system. Assembled with Bushing Extender, provides two in-line elbow interfaces. It can be used for test purpose. The 200A interface allows for live test, visible ground, addition of a 200A tap, or installation of an elbow arrester.
The interface complys with IEEE standard 386, 8.3/14.4 kV, 600 A & 200 A deadbreak design.
Features
* Made of high quality EPDM rubber
* Transition of a 600 A deadbreak system to a 200 A deadbreak or loadbreak system, with the 600A interface connecting to bushing or junction and 200A loadbreak bushing interface
* Fully shielded, submersible connection for deadbreak system
* 100% factory tested
* In compliance with IEC standard 386
Construction


1. Reducing Tap Plug (RTP)
2. Insulating Layer
3. Semi-conducting Insert
4. Grounding Tab
5. Conductive Ring
6. Semi-conducting Shield
Technical Data
| Item | Parameters |
| Voltage Class | 15 kV |
| Voltage Rating | 8.3/14.4 kV |
| Rated Current | 200 A |
| AC Withstand Voltage 5min | 39 kV |
| DC Withstand Voltage 15min | 35 kV |
| Partial Discharge | 15 kV, ≤10 pC |
| BIL | 95 kV |
| Thermal Current | 10 kA, 0.6 s |
| Dynamic Current | 20 kA, 10 ms |
Kit Contents
Bushing Extender
Reducing Tap Plug (RTP)
Bolt
Wipers
Silicone Grease
Installation Instruction
Certificate
Ordering Instructions
| Product | Part Number |
| 15kV Reducing Tap Plug (RTP) | CYS-AFZH-15/600/200 |