Intelligent Precision Power Distribution Unit
Model: LNK- IMPU_8GB10_ZK_GB
Overview
Features
► Use imported 32-bit ARM microprocessor (CPU) control and software programming technology for advanced embedded operating system;
► Use 85 ~ 265Vac global applicable working power technology, achieved level 5 energy efficiency management
► Use 1.3-inch OLED screen with clear display
► isolated RS485 communication port. It adopts standard MODBUS-RTU
► Built-in alarm buzzer
► Built-in clock system and backup power supply
► meeting the requirements of IEC60297 standards;
Technical Indexes
Item | Parameter Requirements | Remark |
Working Power | 85V~265VAC |
|
Working Frequency | 50Hz |
|
Total Input | Specification please see the product label | According to Order Requirement |
Master Switch | Please see the product label | According to Order Requirement |
Voltage Measurement | Range:0~300V | Isolated |
Display Digits:0.01V | ||
Current Measurement | Input: Transformer | Isolated |
Range:0~30mA | Transformer output secondary current | |
Display Digits:0.01A | ||
Branch off | 16A/250Vac Max. |
|
Power on Sequence | Supports power-on sequence output from 1 to 8 branches |
|
Power Measurement | Accuracy:Grade 1 | Active measurement |
Display Digits: 0.01kW | ||
Electricity Measurement | Accuracy:Grade 1 | Active measurement |
Display Digits:0.001kWh | ||
Temperature and Humidity Measurement | Temperature:0.01℃ Humidity:0.01%RH | Optional: But with sensors |
Communication Port | RS485 port, Modbus RTU Communication Protocol | Optional: uplink / downlink |
Display | OLED Screen, Blue text on black / White text on black | Optional |
Alarm Function 1 | Under-voltage, over-voltage, over-current, power out-of-limit alarms | Optional |
Alarm Function 2 | Temperature and humidity alarm | Optional: But with sensors |
Alarm Function 3 | Access control 1, access control 2, smoke detection and flood alarms. | Optional: But with sensors |
Alarm Function 4 | Lightning protection failure detection and lightning protection count | Optional, but with a lightning protection module |
Photosensitive Detection | Normally used for automatic lighting with extended functions | Optional, but with an interface expansion module |
ordering information
Model Number | Installation | Length | Profile specification | Input Connction | Input control | Output control | Output Interface | accessories | Remark |
LNK- IMPU_8GB10_ZK_GB | Horizontal | 19Inch | 1U | Power Cable 1.8m | Micro Circuit Breaker 1P,16A | GB2015,Max=13A,8CH Control output | GB1002(10A/250V) | Smart Meter |
|
LNK- IPMU_8IEC13K_ZK_IEC14 |
Horizontal | 19Inch | 1U | Power Cable 1.8m | Micro Circuit Breaker 1P,16A | IEC320-C13(Cable anti falling),Max=13A,8CH Control output | IEC60320 C13 | Smart Meter |
|
LNK-IPMU_8UL_ ZK_UL |
Horizontal | 19Inch | 1U | Power Cable 1.8m | Micro Circuit Breaker 1P,16A | NEMA5-15R Max=16A,8CH Control output | (16A/250V) | Smart Meter |
|
Note: More Input and output interface type available, please contact us for more details. |
Application