| Product Type Designation |
SINAMICS G120XA (Pump & Fan Dedicated Inverter) |
| Order Number |
6SL3220-1YD56-0CB0 |
| Product Series |
SINAMICS G120XA (Pump & Fan Dedicated Inverter) |
| Application Optimized |
Pump and Fan Applications |
| Operator Panel |
Without HMI Device |
| Integrated Filter |
Yes (Category C3 RFI Suppression Filter) |
| Frame Size |
FSH |
| Protection Degree |
IP20 / UL Open Type |
| Number of Phases |
3 AC |
| Line Voltage Range |
380 V -15% to 440 V +10% (323 V to 484 V) |
| Line Frequency Range |
47 to 63 Hz |
| Rated Power (LO) |
315 kW |
| Rated Current (LO) |
556 A |
| Input Frequency |
50/60 Hz |
| Number of Phases |
3 AC |
| Rated Voltage |
Up to input voltage - 15% (depending on frequency) |
| Rated Power (IEC 400V LO) |
315 kW |
| Rated Current (400V IN) |
556 A |
| Rated Current (380V IN) |
575 A |
| Max Output Current |
612 A (110% overload) |
| Output Frequency Range |
0.00 to 600.00 Hz |
| Pulse Frequency |
2 to 16 kHz (adjustable) |
| Control Principle |
Vector Control (V/f and Sensorless Vector Control) |
| Overload Class |
110% for 60 seconds every 600 seconds |
| Alternative Overload |
135% for 3 seconds or 100% for 240 seconds |
| Continuous Operation |
100% rated current (unlimited time) |
| MODBUS RTU |
Yes |
| BACnet MS/TP |
Yes |
| USS |
Yes |
| PROFINET |
No (Not integrated in this model) |
| Digital Inputs (DI) |
6 (configurable) |
| Digital Outputs (DO) |
4 (configurable, relay and transistor) |
| Motor Temperature Input |
1 (PTC/KTY) |
| Analog Inputs (AI) |
2 (0-10V or 4-20mA, configurable) |
| Analog Outputs (AQ) |
2 (0-10V or 4-20mA, configurable) |
| Cooling Type |
Air Cooling with Integrated Fan |
| Cooling Air Requirement |
1.08 m³/s (38.12 ft³/s) |
| Heatsink Temperature Range |
-20 °C to +90 °C |
| Operating Temperature Range |
0 °C to +45 °C (horizontal installation) |
| Storage/Transport Temperature Range |
-40 °C to +70 °C |
| Relative Humidity |
5% to 95% (non-condensing, 25 °C) |
| Installation Altitude |
Up to 1000 m (sea level) without derating; 1000-2000 m with derating |
| Storage/Transport Air Pressure |
660 to 1080 hPa |
| Standard Board Coating |
Class 3C2 according to IEC 60721-3-3:2002 |
| Width |
300 mm |
| Height |
700 mm |
| Depth |
250 mm |
| Approximate Weight |
125 kg |
| CE Marking |
Yes (according to EU Directives) |
| UL/cUL Marking |
Yes (UL 61800-5-1 and CSA C22.2 No. 274) |
| EMC Directive |
EN 61800-3 Category C3 |
| Low Voltage Directive |
EN 61800-5-1 |
| Machinery Directive |
2006/42/EC |
| Integrated Functions |
Pump/Fan Specific Functions (Multi-pump Control, Pipe Fill, Dry Run Protection, etc.) |
| Energy Saving |
Optimized for Variable Torque Loads (Pumps/Fans) |
| Commissioning Tool |
SINAMICS Startdrive (via USB or Ethernet) |
| IO Expansion |
Without IO Expansion (Basic Configuration) |
| Safety Functions |
Safe Torque Off (STO) Optional |