6.6KV Waterproof Compact Substation Transformer for Distribution Systems
Product Description
Specification
| Rated Voltage | 12/17.5/24kV | 36kV |
|
Standard applicable | IEC 62271 – 202 (IEC 61330) | IEC 62271 – 202 (IEC 61330) |
| Normal ambient temperature | 40 ° C | 40 ° C |
| Maximum ambient temperature | 50 ° C | 50 ° C |
| Enclosure construction | Modular | Modular |
| Ventilation | Natural | Natural |
| Temperature class (Std.) | K 10 | K 10 |
| MV and LV compartment | IP 54 | IP 54 |
| Transformer compartment | IP 23 | IP 23 |
| Rated voltage (kV) | 12/24kV | 36kV |
| Power frequency (kV rms) | 28/50 | 70 |
| Impulse (kV p) | 75/125 | 170 |
| Rated frequency (Hz) | 50/60 | 50/60 |
| Rated normal current (A) | 630 | 630 |
| Breaking capacity (A) | 630 | 630 |
| Making capacity (kA) | 52.5 / 40 | 50 |
| Rated normal current (A) | 630 | 630 |
| Breaking capacity (kA) | 21/16 | 20 |
| Making capacity (kA) | 52.5 / 40 | 50 |
| Rated power (kVA) – oil type | 2500 | 2000 |
| Rated power (kVA) – Dry type | 2500 | 2000 |
| Rated secondary voltage (V) | 433 | 433 |
| Vector group | Dyn 11 | Dyn 11 |
| Tapping range | + 5 in steps of 2.5% | + 5 in steps of 2.5% |
| IP | Yes | Yes |
| Internal arc | Yes | Yes |
| Enclosure class | Yes | Yes |
| Impact test | Yes | Yes |
| Short circuit test on earthing | Yes | Yes |
Production Facilities

Marketing

Our business has covered all over the world.
Material
1.The cabinet door adopts a double beveled edge process, which increases the structural strength of the same material by 50%.
2.The installation holes are all made using a multi-layer stamping and stretching process, which reduces the sliding wire situation by more than 80%.
3.The inlet and outlet holes adopt a composite structure of knockdown holes and square holes, which can be flexibly selected during on-site installation.
4.The box adopts a double folding process, which increases the structural strength of the same material by 50%.
5.The control circuit adopts a composite design of debugging mode and fire protection mode, greatly reducing the burning of fan and water pump equipment designed for fire protection during debugging.