40-500kVA Three Phase In/ Three Phase Out
Application:
Data center, telecom, network, security, lab, metro, hospital, government, military, power, transportation, broadcasting, bank, university, scientific research, petrochemical etc.
Features:
l Full DSP digital control in the process of rectification, inverter, charging and discharging
l Intelligent battery management solution, adopts intelligent “third-order”battery charging and discharging management system, extend battery life
l Input power factor up to 0.999, input harmonic current: <3%, system efficiency above 96.5%
l Smart sleep mode, can set rest time for sleeping rotation, energy saveing
l Intelligent system self-diagnosis, plentiful fault records, large history record storage capacity
l Friendly human machine interface, with big touch screen and keyboard, abundant information
l Three phase in, three phase out, double conversion online system, provide best electricity quality and load protection
l Modular design, supporting hot plug, conveniently maintain on-site
l Excellent load adaptability, overload and short circuit capability
l Digital circulation control technology, high reliability in parallel,upto 3frames,reacching 1500kVA
l With EPO function
l All PCB adopts conformal coating technology
Specification:
| Model | HQ-M400 | HQ-M500 | |
| System Capacity | 400kVA | 500kVA | |
| Power Module Capacity | 40kVA | 50kVA | |
| No. of Modules | 10 | 10 | |
| Main | |||
| Input Wiring | 3Ph+N+PE | ||
| Rated Voltage | 380/400/415VAC (line-line) | ||
| Input Power Factor | >0.99 | ||
| Total Harmonic Distortion | THDi<3% for linear full load, THDi<5% for nonlinear full load | ||
| Voltage Range |
304~478Vac(line-line) 100% load; 228V~304Vac (line-line) load derated from 100%-75% linearly |
||
| Input Frequency | 40Hz~70Hz | ||
| Bypass | |||
| Rated Voltage | 380/400/415VAC (line-line) | ||
| Voltage Range | Default Range +15%~-20%(+10%,+15%,+20%,+25%, +25%-10%,-15%, -20%, -30%,-40% can be set) | ||
| Input Frequency | ±1Hz,±3Hz,±5Hz can be set | ||
| Battery | |||
| Input Voltage | ±240VDC (the number of batteries can be selected from 30 to 44) | ||
| Charging Power | 20% * Power Module | ||
| Charging voltage accuracy | ±1% | ||
| Output | |||
| Rated Voltage | 380/400/415VAC (line-line) | ||
| Rated Frequency | 50/60Hz | ||
| Power Factor | 0.9/1(Option) | ||
| Voltage Accuracy | ≤±1.0%@Steady ;≤±5.0%@ Transient | ||
| Dynamic response | <5% (20% - 80% -20% Step load) | ||
| Dynamic recovery time | < 20ms (0% - 100% -0% Step load) | ||
| THDu | THDu <1%(linear load),THDu<5%( non linear load), | ||
| Overload Capacity |
110% overload for 60 min; 125% overload for 10 min; 150% overload for 1 mins; >150% overload for 200ms |
||
| System | |||
| Efficiency | >96% (Dual Switch mode) | ||
| Display | 10.4 inch Touch Screen+LCD+LED | ||
| IP | IP20 | ||
| Environment | Operating Temperature: 0-40℃;Relative Humidity 0-95%(No condensing) | ||
| Noise | <55dB@1 meter away | ||
| Dimension ( WxDxH mm) and Weight (kg) | |||
| Cabinet Dimension | 1300*1100*2000mm | ||
| Module Dimension | 510*700*135mm | ||
| Cabinet Weight | 450kg | ||
| Module Weight | 44kg | 45kg | |