Pipe Network Type Of Novec1230 Automatic Fire Suppression System
specification | Technical Parameter | |
Filling pressure | 4.2Mpa | 5.6Mpa |
Scale of Protective region for one zone | area:max single-zone is 800m² volume: max single-zone is 3600m³ | |
Spraying time | ≤10s | |
Filling density | ≤950kg/m3 | ≤1080kg/m3 |
power | DC24V/1.6A | |
Nitrogen Pressure of Driving De vice | 6.0±1.0Mpa(20℃) | |
Condition of reserving room for container | temperature: -10~50℃, relative humidity: ≤97% | |
max working pressure | 5.3Mpa | 8.0Mpa |
min working pressure | 4.2Mpa | 4.6Mpa |