FM200 Heptafluoropropane gas cylinder
Product Introduction:
Heptafluoropropane (HFC-227ea) cylinders are a common fire extinguishing device, widely used in industrial, commercial, and domestic settings. The safety and reliability of these cylinders are paramount during use. Our company offers forged stainless steel cylinders with capacities ranging from 70 to 140 liters and a resistance range of 4.2 MPa to 36.6 MPa. These cylinders are designed for rapid refilling of fire extinguishing agents, with each standard cylinder required to maintain a volume of 50 ± 1%.
Through professional calculations by our designers, forging using high-quality materials, and final material analysis and pressure vessel testing, we produce high-quality cylinders that meet international standards.
![]() | ![]() | ![]() |
Pipeline series cylinder dimensions:
| Specification | inner diameter | Bottle thread | Valve outlet aperture | Bottle height | Bottle + container valve height | Total height of bottle + container valve + solenoid valve |
| 40L*5.6MPa | ø300 | M80*2 | 50 | 757±15 | 897±15 | 1057±15 |
| 70L*5.6MPa | ø350 | M80*2 | 50 | 898±10 | 1038±10 | 1198±10 |
| 100L*5.6MPa | ø350 | M80*2 | 50 | 1213±10 | 1353±10 | 1513±10 |
| 120L*5.6MPa | ø350 | M80*2 | 50 | 1414±10 | 1554±10 | 1714±10 |
| 150L*5.6MPa | ø400 | M80*2 | 50 | 1395±10 | 1535±10 | 1695±10 |
| 180L*5.6MPa | ø400 | M80*2 | 50 | 1630±10 | 1770±10 | 1930±10 |
| 70L*17.2 | ø267 | PZ56 | 32 | 1499±10 | 1679±10 | / |
| 90L*17.2 | ø325 | PZ56 | 32 | 1420±10 | 1600±10 | / |
| 120L*17.2 | ø325 | PZ56 | 32 | 1835±10 | 2015±10 | / |
| Specification | inner diameter | Bottle thread | Valve outlet aperture | Bottle height | Bottle + container valve height |
| 80L*17.2MPa | ø279 | M30*1.5 | 14 | 1578±73 | 1738±73 |
| 80L*23.2MPa | ø279 | M30*1.5 | 14 | 1610±70 | 1770±70 |
| 80L*36.6MPa | ø267 | M30*1.5 | 14 | 1770±10 | 1930±10 |
| 90L*17.2MPa | ø325 | M30*1.5 | 14 | 1345±60 | 1505±60 |
| 140L*23.2MPa | ø356 | M30*1.5 | 14 | 1825±20 | 1985±20 |
| 140L*36.6MPa | ø356 | M30*1.5 | 14 | 1825±20 | 198 |
Structural parameters:
| Pressure Switch
| Low Pressure Switch
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| Solenoid Actuator
| Flexible Discharge Hose
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| Pneumatic Actuator
| Flexible Pilot Hose
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| Street Elbow
| Male Tee
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| Nozzle
| Nozzle
|
Valve Assembly
| Body Material | Brass CZ121 |
| Outlet Anti-Recoil Cap Material | CZ122 |
| Max.Working Pressure | 4.2 MPa |
| Working Voltage | DC 24V |
| Maximum Current | 1.6 A |
| Hydraulic Strength Pressure | 6.3 MPa |
| Air Tightness Test Pressure | 5.3 MPa |
| Outlet | 25 mm(1”BSPP) |
| Low Pressure Switch Port | 1/8”NPT |
| Gauge Port | 1/8”NPT |
| Pilot Pressure Port | 1/4”BSPP |
| Overall Size | 175 mm*90mm |
| Weight | 7.26 kg |
| Equivalent Length | 6.096 m(20ft) |

FAQ:
Q: Do you offer other types of fire protection equipment?
A: We offer a full range of FM200 fire protection products, including but not limited to ducted, cabinet, suspended, and cabinet-mounted FM200 systems, IG systems, fire alarms, ventilation systems, and more.
Q: Can you design a complete firefighting system for my factory?
A: Yes. Provide us with the size and area of your factory, and we will have a professional designer provide you with excellent advice.
Q: Can you OEM and establish your own brand?
A: Yes, we offer OEM and ODM services, and you can also establish your own brand on your products.
Q: Can you produce firefighting cans with specific spray paint dimensions?
A: Yes, we are both a manufacturer and a trading company. We have our own factory and welcome your inquiries.