| Deck slope control |  			Can be easily controlled by 1 cylinder |  		
 		 			| Fire board |  			With test deck |  		
 		 			| Temperature control valve |  			Automatic temperature control valve is used |  		
 		 			| Grade A, B temperature & heat output |  			760 ± 28 °C (1400 ± 50 °F) - 21000 ~ 22000 BTU/min (369 ~ 387 KWH) |  		
 		 			| Grade C temperature & heat output |  			704 ± 28 °C (1300 ± 50 °F) - 18000 ~ 19000 BTU/min (316 ~ 334 KWH) |  		
 		 			| Gas delivery test & control methods |  			Different test and control methods are required for each gas delivered to the burner |  		
 		 			| LNG gas flow control |  			Accurate measurement of gas flow with MFM (gas flow controlled by automatic control valve) |  		
 		 			| LPG air flow adjustment |  			Use inverter system to adjust air flow rate: The speed on the test deck is 19 ± 8 km/h (5.5 m/sec) |  		
 		 			| Ignition method |  			The automatic ignition method is adopted, and the test can be automatically ignited at the same time |  		
 		 			| Ventilation duct protection |  			A guide plate is attached to the ventilation duct to protect the airflow turbulence supplied to the test deck from external interference |  		
 		 			| Ventilation duct adjustment |  			A slope adjustment panel is installed on the ventilation duct to adjust the direction of air flow |  		
 		 			| Thermocouple installation & temperature test |  			A thermocouple is installed at 58.7mm at the top of burner 12, and the temperature can be tested at 888 ± 28 °C |  		
 		 			| Test control system |  			The DAQ system can automatically control and complete the test |