| Model NO. | EA16 | EA16-400Hz |
| Sensing Input | Voltage 170~510 VAC single phase 2 wire | Voltage 170~510 VAC single phase 2 wire |
| Frequency 50/60 Hz | Frequency 400 Hz |
| Power Input | Voltage 60~300 VAC single phase 2 wire | Voltage 60~300 VAC single phase 2 wire Max. 90 VDC @ 240 VAC input |
| Output | Voltage Max. 90 VDC @ 240 VAC input Current Continuous 16A, Max. Intermittent 20A for 10 sec. Resistance Min. 6 Ohm @ 35 VDC | Voltage Max. 90 VDC @ 240 VAC input Current Continuous 16A, Max. Intermittent 20A for 10 sec. Resistance Min. 6 Ohm @ 35 VDC |
| Voltage Regulation | < ±0.5% (with 4% engine governing) | < ±0.5% (with 4% engine governing) |
| Voltage Build-up | Residual volts at AVR terminal > 5 VAC | Residual volts at AVR terminal > 5 VAC |
| External Volts Adjustment | ±5% with 2 K Ohm 1 watt trimmer | ±5% with 2 K Ohm 1 watt trimmer |
| Unit Power Dissipation | Max. 10 watt | Max. 10 watt |
| Thermal Drift | 0.03% per °C change in AVR ambient | 0.03% per °C change in AVR ambient |
| Under Frequency Protection | 55 Hz @ 60 Hz / 45 Hz @ 55 Hz (Adjustable) | 360 Hz (Adjustable) |
| CT Current Compensation Input | 1A or 5A (Selectable) | 1A or 5A (Selectable) |
| Analogue Input | ±5 VDC ±10% AC @ ±3 VDC | ±5 VDC ±10% AC @ ±3 VDC |
| Environment | Operating Temperature : -40~70 °C Storage Temperature : -40~85 °C Relative Humidity : Maximum 95% Vibration : 3.3G @ 100~2 KHz | Operating Temperature : -40~70 °C Storage Temperature : -40~85 °C Relative Humidity : Maximum 95% Vibration : 3.3G @ 100~2 KHz |
| AVR Controls Functions | VOLT : Voltage Adjustment STAB : Stability Adjustment U/F*: To Set the U/F Knee Point DROOP : To Adjust Droop TRIM : Analogue Input Adjustment (*U/F: Under Frequency Protection) | VOLT : Voltage Adjustment STAB : Stability Adjustment U/F*: To Set the U/F Knee Point DROOP : To Adjust Droop TRIM : Analogue Input Adjustment (*U/F: Under Frequency Protection) |
| Dimensions | 156.0 (L) x 106.0 (W) x 43.0 (H) mm | 156.0 (L) x 106.0 (W) x 43.0 (H) mm |
| Weight | 450 g ±2% | 450 g ±2% |