LW30 series 3 Phase Universal Isolator switch Main Switch with “ON-OFF”
Advantage:
- LW30 series Rotary Isolator switch have the characteristics of small size, multi-function, compact structure, exquisite material selection, good insulation, flexible conversion operation, safety and reliability, and novel appearance.
- LW30 series Rotary Isolator switch supply for many different Installation method: Padlock-Panel, Panel Mounting, DIN-RAIL Mounting…
Product Description:
- LW30 series Rotary Isolator switch applied to circuits of AC 50Hz/60Hz with working voltage up to 440V and rated working current up to 100A.
- LW30 Series Rotary Isolator switch is suitable to control: air-conditioner, water pump and ventilating equipment, and AC motors with small power..
- LW30 series Rotary Isolator switch have six current ratings: 20A,25A,32A,40A,63A,80A,100A
- LW30 series Rotary Isolator switch has the finger protection terminals, which offers an extra advantage.
- LW30 series Rotary Isolator switch has Larger insulation distance, quick disconnector response. And is a good choice For DC circuits.
- LW30 series Rotary Isolator switch has additional contact which enable us to install the contact separetely.
- LW30 series Rotary Isolator switch comply with IEC 60947-3.
Technical parameters:
| Description | LW30-25(20) | LW30-32 | LW30-40 | LW30-63 | LW30-80 |
| Rated thermal current | ITH | A | 25(20) | 32 | 40 | 63 | 80 |
| Rated working voltage | LE | V | 240 | 440 | 240 | 440 | 240 | 440 | 240 | 440 | 240 | 440 |
| Ie/Pe | Ie/Pe | | | | | | | | | | | |
| AC-21A | | A/KW | 20/- | 20/- | 32/- | 32/- | 40/- | 40/- | 63/- | 63/- | 80/- | 80/- |
| AC-22A | | A/KW | 20/- | 20/- | 32/- | 32/- | 40/- | 40/- | 63/- | 63/- | 80/- | 80/- |
| AC-23A | | A/KW | 15/4 | 15/7.5 | 22/5.5 | 22/11 | 30/7.5 | 30/15 | 43/11 | 43/22 | 57/18.5 | 57/30 |
| AC-3 | | A/KW | 11.7/3 | 11.7/5.5 | 15/4 | 15/7.5 | 22/7.5 | 22/11 | 36/11 | 36/18.5 | 43/15 | 57/30 |

| Description | Dimensions(mm) | Installation(mm) |
| A | B | C | K | L | E | F | D1 | D2 |
| LW30-20 | 64 | 42 | 54 | 13.5 | 61 | 48 | 48 | Φ10 | Φ4.2 |
| LW30-25 | 64 | 42 | 54 | 13.5 | 61 | 48 | 48 | Φ10 | Φ4.2 |
| LW30-32 | 64 | 42 | 54 | 13.5 | 61 | 48 | 48 | Φ10 | Φ4.2 |
| LW30-40 | 64 | 50 | 64 | 16 | 67 | 48 | 48 | Φ10 | Φ4.2 |
| LW30-63 | 64 | 50 | 64 | 16 | 67 | 48 | 48 | Φ10 | Φ4.2 |
| LW30-80 | 64 | 70 | 80 | 22.5 | 82 | 48 | 48 | Φ10 | Φ4.2 |
| LW30-100 | 64 | 70 | 80 | 22.5 | 82 | 48 | 48 | Φ10 | Φ4.2 |
Normal working conditions:
- Working temperature: -25°C~+40°C;the average temperature mustn’t be pass 35°C
- Working height: ≤2,000m
- Relative humidity: ≤50% with highest temperature +40°C,but allow higher humidity with low temperature less than 40°C.(eg. humidity 90%----teperature20°C)
Classification
1. Classified by utilization, control and load switch.
Main switch Control switch
2. Classified by Usages
AC-23A AC-3
- Classified by Protection level
Without Water-proof box:IP2L0 With Water-proof box:IP65