Cast Resin Busduct Manufacturer customized 1600A FSMC waterproof casting type bus duct insulated resin bus duct
Dense Bus Duct Selection Parameters
| Current Level |
XLC /4P W(mm) |
XLC /4P H(mm) |
XLC /5P W(mm) |
XLC /5P H(mm) |
| 400 | 128 | 98 | 128 | 98 |
| 500 | 128 | 108 | 128 | 108 |
| 630 | 128 | 123 | 128 | 123 |
| 800 | 128 | 138 | 128 | 138 |
| 1000 | 128 | 158 | 128 | 158 |
| 1250 | 128 | 183 | 128 | 183 |
| 1600 | 128 | 218 | 128 | 218 |
| 2000 | 128 | 268 | 128 | 268 |
| 2500 | 128 | 280 | 128 | 280 |
| 3200 | 128 | 400 | 128 | 400 |
| 4000 | 128 | 490 | 128 | 490 |
XLC Type Bus Duct Technical Parameters
| Execution Standards | IEC60439.1-2000 IEC60439.2-2000 GB/T 7251.6-2015 |
| Ambient Temperature | -5/+40°C (24-hour average temperature not exceeding 35°C) |
| Altitude | Not exceeding 2000M |
| Protection Grade | IP54, IP66 |
| Unit Length | Choose between 1.6, 2.5, 3.2, 6 (0.5-6) meters |
| Rated Operational Voltage | 690V (with tap unit)/1000V (without tap unit) |
| Rated Insulation Voltage (Ui) | 800V (with tap unit)/1000V (without tap unit) |
| Frequency | 50-60 HZ |
Electrical Performance Specifications
| Rated Current (A) |
Resistance (uΩ/m) |
Reactance (uΩ/m) |
Total Reactance (uΩ/m) |
| 400 | 88.9 | 66.5 | 289.7 |
| 630 | 71.1 | 62.2 | 289.7 |
| 800 | 56.4 | 39.1 | 184.2 |
| 1000 | 40.3 | 37.9 | 176.3 |
| 1250 | 33.2 | 46.6 | 221.6 |
| 1600 | 24.5 | 30.1 | 150.7 |
| 2000 | 19.5 | 7.4 | 130.7 |
| 2500 | 14.5 | 25.9 | 129.6 |
| 3150 | 11.3 | 25.3 | 120.9 |
| 4000 | 8.9 | 14.3 | 76.2 |
| 5000 | 6.7 | 13 | 69 |
Additional Technical Specifications
| Rated Short-time Withstand Current | 30, 30, 50, 50, 80 KA |
| Rated Peak Withstand Current | 63, 63, 105, 105, 176 KA |
| Temperature Rise | ≤70 K |
| Insulation Resistance | ≥20 MΩ |
| Electrical Clearance | ≥10.0mm (with tapping unit)/≥14.0mm (without tapping unit) |
| Creepage | ≥12.5mm (with tap cell)/≥16.0mm (without tap cell) |
| Protection Circuit Effectiveness | <0.02 Ω |
| Dielectric Properties | 50Hz, 3750v/min, no breakdown, flashover |
| Installation Method | Vertical or horizontal |
| Number of Plug-in Interfaces | Minimum 0.5/m pieces (double-sided plug can be provided) |
| Maximum Fixed Spacing | 4, 4, 3, 3 meters |
| Balanced Load | 20, 20, 25, 30 kg/m |
| Concentrated Load | 90, 90, 90, 90 kg |
Key Features
- Safety, aesthetics, and reliability advantages
- Strong overload capacity
- Low temperature rise
- Excellent load capacity and dynamic/thermal stability
- Eliminates uneven current distribution in spliced high-voltage cables
- Double-grounded shell for high safety performance
- Good short-circuit resistance and low energy consumption
- Convenient and quick maintenance, disassembly, and assembly
Application Fields
Power supply systems of large factories, mining enterprises, large substations, captive power plants, from generators to step-up transformers, and from transformers to high-voltage distribution rooms.
Casted Busway Features
- Large capacity range from 100A to 4000A
- High protection level up to IP68 (100% waterproof and dustproof)
- Epoxy resin casting structure prevents metal oxidation and corrosion
- Low line voltage drop with high instantaneous current withstand value
- High structural strength, good mechanical properties, maintenance-free
- Compact structure, small size, strong dynamic and thermal stability
- Suitable for harsh indoor/outdoor environments with good stability
- Capable of continuous operation under overload conditions
Casted Busway Applications
Power plants, substations, shipbuilding, paper making, ports, basements, petrochemical industries, steel smelting, coal mines, and other harsh environments.
Fire-Resistant Bus Duct Features
- 180-minute fire-resistant duration
- Compact and dense structure with small size
- Fire-resistant paint coating and baffles prevent flame/gas entry
- Low impedance with excellent dynamic and thermal stability
- Easy and quick maintenance, disassembly and assembly
- Fireproof materials withstand temperatures up to 1000°C
- Excellent electrical conductivity
- Suitable for various fire risk areas ensuring continuous power supply
Fire-Resistant Applications
Teaching buildings, high-rise hospitals, high-rise hotels, financial buildings, office buildings, urban rail transit, government offices, large libraries, cotton spinning and mining enterprises.
Advanced Structural Features
- Fully meets load demands
- Ultra-thin, compact, and aesthetically pleasing design
- 360-degree comprehensive protection against dust, corrosion, moisture, water, rust, and impact
- "Sandwich" structure with compact integration of shell, insulation, and conductor
- Unique "亞" shape structure with excellent load-bearing capacity
- Sawtooth shape design with oversized heat dissipation surface
- Critical structural design integrating consumables, strength, and heat dissipation
- Dual neutral system for safer electricity usage
- Non-magnetic shell design eliminates magnetic eddy current interference
Universal Applications
Shopping malls, schools, industrial plants, rail transit, commercial complexes, real estate developments, data centers, hospitals, and hotels.