IP66 Plug In Busway 100A 250A 400A 630A Dense Electrical Busbar
Product Overview
High-performance electrical busduct slot plug-in box designed for dense busbar applications. Available in current ratings of 100A, 250A, 400A, and 630A, this distribution box provides reliable power distribution solutions for industrial applications.
Custom Solutions
We offer comprehensive busbar trunking products and can customize solutions to meet your specific requirements. Contact us via email or WhatsApp for personalized assistance and technical support.
Dense Bus Duct Selection Parameters
| Current Level |
XLC /4P W(mm) |
XLC /4P H(mm) |
XLC /5P W(mm) |
XLC /5P H(mm) |
| 400 | 128 | 98 | 128 | 98 |
| 500 | 128 | 108 | 128 | 108 |
| 630 | 128 | 123 | 128 | 123 |
| 800 | 128 | 138 | 128 | 138 |
| 1000 | 128 | 158 | 128 | 158 |
| 1250 | 128 | 183 | 128 | 183 |
| 1600 | 128 | 218 | 128 | 218 |
| 2000 | 128 | 268 | 128 | 268 |
| 2500 | 128 | 280 | 128 | 280 |
| 3200 | 128 | 400 | 128 | 400 |
| 4000 | 128 | 490 | 128 | 490 |
XLC Type Bus Duct Technical Specifications
- Execution Standards: IEC60439.1-2000, IEC60439.2-2000, GB/T 7251.6-2015
- Ambient Temperature: -5°C to +40°C (24-hour average not exceeding 35°C)
- Altitude: Up to 2000 meters
- Protection Grade: IP54, IP66
- Unit Length: 0.5-6 meters (standard: 1.6, 2.5, 3.2, 6)
- Rated Operational Voltage: 690V (with tap unit) / 1000V (without tap unit)
- Rated Insulation Voltage (Ui): 800V (with tap unit) / 1000V (without tap unit)
- Frequency: 50-60 Hz
Electrical Performance Data
| Rated Current (A) |
Resistance (uΩ/m) |
Reactance (uΩ/m) |
Total Reactance (uΩ/m) |
Voltage Drop (mV/m) |
| 400 | 88.9 | 66.5 | 289.7 | 77.5 |
| 630 | 71.1 | 62.2 | 289.7 | 81 |
| 800 | 56.4 | 39.1 | 184.2 | 77.3 |
| 1000 | 40.3 | 37.9 | 176.3 | 77.5 |
| 1250 | 33.2 | 46.6 | 221.6 | 76.4 |
| 1600 | 24.5 | 30.1 | 150.7 | 74.9 |
| 2000 | 19.5 | 7.4 | 130.7 | 73.3 |
| 2500 | 14.5 | 25.9 | 129.6 | 71.4 |
| 3150 | 11.3 | 25.3 | 120.9 | 69.7 |
| 4000 | 8.9 | 14.3 | 76.2 | 63 |
| 5000 | 6.7 | 13 | 69 | 61.4 |
Additional Technical Parameters
- Rated Short-time Withstand Current: 30, 30, 50, 50, 80 KA
- Rated Peak Withstand Current: 63, 63, 105, 105, 176 KA
- Temperature Rise: ≤70 K
- Insulation Resistance: ≥20 MΩ
- Electrical Clearance: ≥10.0mm (with tapping unit) / ≥14.0mm (without tapping unit)
- Creepage: ≥12.5mm (with tap cell) / ≥16.0mm (without tap cell)
- Protection Circuit Effectiveness: <0.02 Ω
- Dielectric Properties: 50Hz, 3750V/min, no breakdown or flashover
- Installation Method: Vertical or horizontal
- Number of Plug-in Interfaces: Minimum 0.5/m (double-sided plug available)
- Maximum Fixed Spacing: 4, 4, 3, 3 meters
- Balanced Load: 20, 20, 25, 30 kg/m
- Concentrated Load: 90, 90, 90, 90 kg