Specifications
Place of Origin :
Wuhan,Hubei,China
Brand Name :
Huaying
Certification :
ISO CE
Model Number :
HYVA-404
Description

Introduction

Tests for Current Transformer:
1)Excitation curve and parameters test
2)Turns ratio test
3)Ratio and phase error test
4)Polarity mark check
5)Coil resistance measurement
6)Secondary loop burden measurement
7)Error line curve test for protection CT
8)Transient CT parameters test
9)CT nameplate guess
10)Saturation hysteresis loop curve measurement

Tests for Voltage Transformer:

1)Turns ratio test and phase angle error test
2)Polarity test
3) Secondary burden test
4) Coil resistance test

Application

1) CT nameplate check
2) CT parameters check in work burden
3) CT transient parameters analysis
4) CT ratio and phase error calibration
5) PT routine test

Technical index

1 Test standards: IEC60044-1, IEC60044-6, GB1208, GB16847, C57.13
2 Power supply: AC220V±10%,50Hz/60Hz±10%
3 Power output: 0.1~180V (AC)
4 Current output: 0.001~5A(RMS)
5 Power output:300VA
6 Maximum knee voltage measurement:45kv
7 Current measurement:
Range:0~10A (automatically change range in 0.1/0.4/2/10A)
Error <±0.1%+0.01%FS
8 Voltage measurement:
Range:0~200 V (automatically change range in 1V/10V/70V/200V)
Error < ±0.1%+0.01%FS
9 Turns ratio measurement:
Range :1~35000,
1~2000 error<0.05%
2000~5000 error>0.1%
5000~35000 error<0.2%
10 Phase measurement: error:±2min,resolution:0.01min
11 Coil resistance measurement:
Range:0~8kΩ (automatically change range in 2ohm/20ohm/80ohm/800ohm/8kohm)
Error< 0.2%RDG+0.02%FS
Maximum resolution:0.1mΩ
12 Temperature measurement:-50~100 Celsius degree, error<3 Celsius degree
13 CT Secondary burden:
Range 0~160ohm (automatically change range in 2ohm/20ohm/80ohm/160ohm)
Error <0.2%RDG+0.02%FS
Maximum resolution 0.001ohm
14 PT Secondary burden:
Range 0~80kohm (automatically change range in 800ohm/8kohm/80kohm)
Error <0.2%RDG+0.02%FS
Maximum resolution: 0.1ohm
15 PT ratio measurement:
Range :1~35000,
1~5000 error<0.2%
5000~35000 error<0.5%
16 Saved data groups:>1000groups
17 Work condition: Temperature:-10℃~50℃, moist:≤90%
18 Size: 485mm×356mm×183mm
19 Weight: <15Kg

Tags

ct analyzer, ct pt analyzer, current transformer analyzer, potential transformer analyzer,testing equipment,lab test equipment,made in china, alibaba gold supplier,measuring and testing equipment.

HYVA-404 CT PT Analyzer

Send your message to this supplier
Send Now

HYVA-404 CT PT Analyzer

Ask Latest Price
Place of Origin :
Wuhan,Hubei,China
Brand Name :
Huaying
Certification :
ISO CE
Model Number :
HYVA-404
Contact Supplier
HYVA-404 CT PT Analyzer

Wuhan Huaying Electric Power Tech & Science Co.,ltd

Verified Supplier
12 Years
Hubei, Wuhan
Since 1997
Business Type :
Manufacturer,Exporter,Seller
Total Annual :
$50,000,000-$100,000,000
Employee Number :
100-150
Certification Level :
Verified Supplier
Contact Supplier
Submit Requirement