Electrical Specifications |
Maximum voltage to earth ground |
1000 V |
Battery type |
AA alkaline IEC/EN LR6 (x4) |
Battery life |
More than 15 hours* |
* In Ground Resistance measurement mode, with backlight turned off, and RF mode turned off |
Frequency range |
40 Hz to 1 kHz |
Ingress protection |
IEC/EN 60529: IP30 with jaw closed |
LCD |
Digital reading |
9999 counts |
Refresh rate |
4 per second |
Operating temperature |
-10 °C to + 50 °C |
|
Storage temperature |
-20 °C to + 60 °C |
Operating humidity |
Non condensing (<10 °C) (< 50 °F) |
≤90% RH (at 10 °C to 30 °C [50 °F to 86 °F]) |
≤75% RH (at 30 °C to 40 °C [86 °F to 104 °F]) |
≤45% RH (at 40 °C to 50 °C [104 °F to 122 °F]) |
(Non condensing) |
Operating altitude |
2000 m (6561 feet) |
Storage altitude |
12 000 m (39,370 feet) |
Reference temperature |
23 °C ±5 °C (73 °F ±9 °F) |
Temperature coefficient |
0.15% x (specified accuracy)/ °C (<18 °C or >28 °C [<64.4 °F or >82.4 °F]) |
Overload indication |
OL |
Data logging capacity |
Minimum of 32,760 measurements |
Data logging interval |
1 second to 59 minutes and 59 seconds |
Display reading specification with standard loop resistance |
Input (Ω) |
Minimum |
Maximum |
0.474 |
0.417 |
0.531 |
0.5 |
0.443 |
0.558 |
10 |
9.55 |
10.45 |
100 |
96 |
104 |
Safety |
General |
IEC/EN 61010-1: Pollution Degree 2 IEC/EN 61557-1 |
Measurement |
IEC/EN 61010-2-032: CAT IV 600 V / CAT III 1000 V |
Current clamp for leakage current measurements |
IEC/EN 61557-13: Class 2, ≤30 A/m |