Specifications
Brand Name :
Hima
Model Number :
HIMATRIX F3DIO 8/8 01 F3 DIO 8/8 01
Place of Origin :
Germany
MOQ :
1
Price :
66USD
Payment Terms :
T/T
Supply Ability :
in stock
Delivery Time :
2-3 work days
Packaging Details :
Brand new and original
Product Parameters :
Remote I/O module
Response time :
≥ 10 ms
Ethernet interfaces :
2 x RJ-45, 10BASE-T/100BASE-Tx with integrated switch
Current input :
max. 8 A
Fuse (external) :
10 A time-lag (T)
Back-up battery :
None
Operating temperature :
0...+60 °C
Storage temperature :
-40...+85 °C
Description
Hima HIMATRIX F3DIO 8/8 01 F3 DIO 8/8 01 Remote I/O module with 8 Digital Inputs 8 Digital Outputs
The safety-related F3 DIO 8/8 01 remote I/O is a compact unit built in a metal housing and equipped with 8 digital inputs, 8 digital DO+ outputs (L- ground), 2 digital DO- outputs (S+ ground), and 2 pulsed outputs. The digital outputs DO4+, DO8+, DO4-, and DO8- can also be wired as 2-pole connections when needed. The module is available in several model variants for both SILworX and ELOP II Factory, as shown in the screen referenced.
These remote I/O units connect to individual HIMax or HIMatrix controllers over safeethernet. Their job is to expand the I/O capacity of a system, and they don't run any user program on their own.
F3 DIO 8/8 Model Variants
Designation I/O Configuration Operating Temp. Programming Tool Additional Standards (Ruggedization)
F3 DIO 8/8 01 8 DI / 8 DO / 2 Pulsed Outputs 0...+60 °C ELOP II Factory Standard
F3 DIO 8/8 014 8 DI / 8 DO / 2 Pulsed Outputs -25...+70 °C (Class T1) ELOP II Factory Vibration & Shock Tested:
• EN 50125-3
• EN 50155
• IEC 61373 (Class 1B)
F3 DIO 8/8 01 (SILworX) 8 DI / 8 DO / 2 Pulsed Outputs 0...+60 °C SILworX Standard
F3 DIO 8/8 014 (SILworX) 8 DI / 8 DO / 2 Pulsed Outputs -25...+70 °C (Class T1) SILworX Vibration & Shock Tested:
• EN 50125-3
• EN 50155
• IEC 61373 (Class 1B)
Key Differences Summary
01 vs. 014: The 01 is the standard model. The 014 is the rugged version built for wider temperature ranges and high-vibration environments (like rail or heavy transport).
Software: You must select the model that matches your specific software environment (ELOP II Factory vs. SILworX).
Hima HIMATRIX F3DIO 8/8 01 F3 DIO 8/8 01 Remote I/O module with 8 Digital Inputs 8 Digital Outputs
While the system is being booted, all LEDs are lit simultaneously.
LED Color Status Description
RUN Green On Device in RUN, normal operation


Blinking Device in STOP; a new operating system is being loaded


Off Device is not in the RUN state
ERROR Red On Device is in ERROR STOP state; internal fault detected by self-tests (e.g., hardware faults or cycle time overrun). The processor can only be restarted via PADT (reboot).


Blinking ERROR blinks and all other LEDs light simultaneously when the boot loader detects an OS fault in flash memory and waits for a new OS to be loaded


Off No faults detected
PROG Yellow On A new configuration is being loaded


Blinking Device switches from INIT to STOP; a new OS is being written to flash ROM


Off No configuration or OS is being loaded
FORCE Yellow Off The FORCE LED of a remote I/O is not functioning; FORCE LED of the controller signals forcing of a remote I/O
FAULT Yellow On Loaded configuration is not valid; new OS is corrupted (after OS download)


Blinking Fault while loading a new OS; one or multiple I/O faults occurred


Off No faults occurred
OSL Yellow Blinking Operating system emergency loader active


Off Emergency loader inactive
BL Yellow Blinking OS and OSL binary defective or hardware fault (INIT_FAIL)


Off No faults occurred
Hima HIMATRIX F3DIO 8/8 01 F3 DIO 8/8 01 Remote I/O module with 8 Digital Inputs 8 Digital Outputs
Line Control Purpose
Line control is used to detect short-circuits or open-circuits and can be configured for remote I/O, e.g., on EMERGENCY STOP inputs compliant with Cat. 4 and PL e according to EN ISO 13849-1.
Connection Setup
01. Digital Output to Input Loop:
Connect the system's digital outputs TO 1 through TO 2 to the digital inputs DI of the same system.
02. Pulsed Line Detection:
The remote I/O continuously pulses the outputs to detect:
• Short-circuits
• Open-circuits
on the lines connected to the digital inputs.
03. Configuration:
In SILworX, configure the pulsed outputs via:
Value [BOOL] -> system variable
In ELOP II Factory, use:
DO[01].Value system signal
Note: The variables for pulsed outputs must:
• Begin with channel 1
• Be in direct sequential order
Hima HIMATRIX F3DIO 8/8 01 F3 DIO 8/8 01 Remote I/O module with 8 Digital Inputs 8 Digital Outputs
$2 Billion+ in Inventory Value.
20 Million+ Items in Stock.
20 Years of Technology Covered.
Why upgrade if you don't have to?
We specialize in both New and Discontinued components. Whether you are running the latest setup or maintaining a legacy system, we have the part on the shelf.
What we ship daily:
  • Control: DCS, PLC, CNC, SPS
  • Visualization: HMIs, Display Panels, Panel Controllers
  • Motion: Frequency Inverters, Servos, Motors
  • Essentials: Industrial PCs, Power Supplies
Excellence isn't a buzzword here.
It's about delivery efficiency and getting you the right part, right now.
Need a quote? Text me.
Contact Information
Miya Zheng
Sales Manager @ Amikon

Mobile: +86 180 2077 6792
Send your message to this supplier
Send Now

Hima HIMATRIX F3DIO 8/8 01 F3 DIO 8/8 01 Remote I/O module with 8 Digital Inputs 8 Digital Outputs

Ask Latest Price
Watch Video
Brand Name :
Hima
Model Number :
HIMATRIX F3DIO 8/8 01 F3 DIO 8/8 01
Place of Origin :
Germany
MOQ :
1
Price :
66USD
Payment Terms :
T/T
Contact Supplier
video
Hima HIMATRIX F3DIO 8/8 01 F3 DIO 8/8 01 Remote I/O module with 8 Digital Inputs 8 Digital Outputs
Hima HIMATRIX F3DIO 8/8 01 F3 DIO 8/8 01 Remote I/O module with 8 Digital Inputs 8 Digital Outputs
Hima HIMATRIX F3DIO 8/8 01 F3 DIO 8/8 01 Remote I/O module with 8 Digital Inputs 8 Digital Outputs

AMIKON LIMITED

Verified Supplier
2 Years
fujian, xiamen
Since 2004
Business Type :
Trading Company
Total Annual :
85682000-125000000
Employee Number :
70~80
Certification Level :
Verified Supplier
Contact Supplier
Submit Requirement