S/N |   			  			Name |   			  			Unit |   			  			Parameter |   		|||||
  			1 |   			  			rated voltage |   			  			kV |   			  			40.5 |   		|||||
  			2 |   			  			rated frequency |   			  			Hz |   			  			50 |   		|||||
  			3 |   			  			rated current |   			  			A |   			  			630 |   		|||||
  			4 |   			  			rated current of fuse |   			  			100 |   		||||||
  			5 |   			  			rated short time withstand current |   			  			kA |   			  			12.5 |   		|||||
  			6 |   			  			rated short circuit duration |   			  			s |   			  			4 |   		|||||
  			7 |   			  			rated short circuit making current |   			  			kA |   			  			31.5 |   		|||||
  			8 |   			  			Rated peak withstand current |   			  			 |   			  			31.5 |   		|||||
  			9 |   			  			Rated load breaking current |   			  			A |   			  			630 |   		|||||
  			10 |   			  			Rated jump (connect) breaking current (For 100A Fuse) |   			  			2000 |   		||||||
  			11 |   			  			Earthing switch making current |   			  			kA |   			  			31.5 |   		|||||
  			12 |   			  			FT16-40.5FT16-40.5 Resistance of main circuit |   			  			uW |   			  			180 |   		|||||
  			13 |   			  			FT16-40.5RFT16-40.5R Resistance of main circuit |   			  			400 |   		||||||
  			14 |   			  			Opening time |   			  			ms |   			  			95+20 |   		|||||
  			15 |   			  			Rated breaking current of fuse |   			  			kA |   			  			31.5 |   		|||||
  			16 |   			  			Rated insulation level |   			  			1minpower frequency withstand voltage (effective value) |   			  			Phase to phase, Phase to earth |   			  			kV |   			  			95 |   		|||
  			Distance |   			  			115 |   		|||||||
  			Lightning impulse withstand voltage (peak) |   			  			Phase to phase, Phase to earth |   			  			185 |   		||||||
  			Distance |   			  			215 |   		|||||||
  			17 |   			  			1min power frequency withstand voltage of secondary circuit |   			  			2 |   		||||||
  			18 |   			  			Protection level |   			  			HXGT16 |   			  			 |   			  			IP2X |   		||||
  			DFT16 |   			  			 |   			  			IP33 |   		||||||
  			19 |   			  			Center distance of three phases |   			  			 |   			  			420±3 |   		|||||
  			    			20 |   			  			Dimensions |   			  			HXGT16 |   			  			Width |   			  			mm |   			  			1400,1600,2100 |   		|||
  			Depth |   			  			1600 |   		|||||||
  			Height |   			  			2200 |   		|||||||
  			DFT16 |   			  			Width |   			  			1800 |   		||||||
  			Depth |   			  			2300 |   		|||||||
  			Height |   			  			1900 |   		|||||||
  			21 |   			  			Mechanical life of load switch |   			  			Load isolating |   			  			times |   			  			2000 |   		||||
  			Earthing |   			  			2000 |   		|||||||