Ultra Cold Climate Central Air Conditioning Heat Pump For Office, Hospital, School, Shopping mall
Brief Introduction
- The ultra-low temperature air-enhanced compressor is used to achieve stable operation at -25 °C, and the heating at -20 °C is stable without attenuation.
- One machine has two functions (cooling, heating )is more economical than air conditioner
- The module combination is convenient to install. Each module unit has an independent frame structure, refrigeration system, power distribution system, control system and protection system. When one module unit fails, it does not affect the normal operation of other module units.
- Control complete operation, advanced intelligent control system, with compressor protection, high voltage protection, low voltage protection, water shortage protection, leakage protection, lack of protection, overload protection, antifreeze protection, excessive exhaust temperature protection. The comprehensive protection function principle is convenient and simple.
- Easy to install, on roof, in floor or other places.The unit is quick and easy to install and is not subject to installation restrictions.
Technical data
| Model | SLNC-075Ycode name.pdf |
| Compressor capacity | 25HP |
| Function | Heating and Cooling |
| Electricity | 380V-3N-50Hz |
| Working conditions | ℃ | -25~+45 |
| Data | Heata | Nominal capacity | KW | 44.5 |
| Input power | KW | 18.3 |
| COP | / | 2.4 |
| Heating IPLV(H) | 2.7 |
| Coolb | Nominal capacity | KW | 62 |
| Input power | KW | 20.7 |
| COP | / | 3 |
| Cooling IPLV(C) | 2.7 |
| A7W35c | KW/COP | 75.0/4.2 |
| A2W35 | KW/COP | 62.5/3.20 |
| A-7W35 | KW/COP | 50/2.9 |
| A-15W55 | KW/COP | 45.5 /1.97 |
| A-20W45 | KW/COP | 37.4/2.04 |
| Max. running currency | A | 56 |
| Compressor quantity | set | 2 |
| Refrigerant/charging quantity kg | / | R22/15*2 |
| Air blow type | / | Top |
| Water pipe diameter | mm | 50 |
| Rating flow | m³/h | 12.6 |
| Water side pressure loss | kPa | ≤45 |
| Noise level | dB(A) | 62 |
| Overall dimensions(L×W×H) | mm | 2100×1100×2080 |
| Weight | kg | 730 |
a: Nominal heating conditions: ambient dry bulb temperature-12℃, wet bulb temperature-14℃, outlet water temperature 41℃, water flow 0.172 * nominal heating capacity
b:Nominal refrigeration conditions: ambient dry bulb temperature 35℃, outlet water temperature 7℃, water flow 0.172 * nominal cooling capacity
c:A7W35 working condition: inlet air temperature 7℃, outlet water temperature 35℃
YUSHEN Products
- It could work in extreme environment /Suitable for environmental temperature:-25℃ to +45 ℃ /-13℉ to 113 ℉
- Quality Components such as Copeland compressor, Danfoss valves
- 100% finished products testing
- Having only one unit which could both heat and cool to maintain means lower repair costs and less work in general