Professional Modular Li-ion Battery Energy Storage Solution for Industrial & Commercial Scenarios
Camel Energy's ICHES Series Cabinet-type Energy Storage System is a highly integrated, modular rechargeable lithium iron phosphate battery solution engineered for flexible industrial and commercial energy storage demands. The compact all-in-one cabinet design integrates high-performance LFP battery modules, intelligent main control, distribution components, integrated air-conditioning temperature control, cabinet-level fire protection, and safety systems—with optional energy storage inverter for complete energy storage deployment.
| Item | ICHES-30 | ICHES-40 | ICHES-50 | ICHES-60 |
|---|---|---|---|---|
| Number of Battery Modules | 6 | 8 | 10 | 12 |
| Rated Energy | 30kWh | 40kWh | 50kWh | 60kWh |
| System Nominal Voltage | 307.2Vdc | 409.6Vdc | 512Vdc | 614.4Vdc |
| System Voltage Range | 268.8~345.6Vdc | 358.4~460.8Vdc | 448~576Vdc | 537.6~691.2Vdc |
| Max. Continuous Charge Current | 100A | 100A | 100A | 100A |
| Max. Continuous Discharge Current | 100A | 100A | 100A | 100A |
| Category | Parameter |
|---|---|
| Dimensions (W*H*D) | 840*2120*955mm (inverter not included) |
| Net Weight | 580kg (30kWh) / 670kg (40kWh) / 760kg (50kWh) / 850kg (60kWh) |
| Protection Grade | IP55 |
| Installation Method | Hoisting & floor fixing (expansion bolt) |
| Working Altitude | Max. 2000m |
| Working Humidity | 5%~90% RH (no condensation) |
| Charging Temperature | 0℃ ~ 50℃ |
| Discharging Temperature | -20℃ ~ 55℃ |
| Storage Temperature | -10℃ ~ 35℃ (recommended) |
| Component | Core Specs |
|---|---|
| Integrated Air-conditioning | Rated Voltage: 220Vac; Cooling Capacity: 2000W; Heating Capacity: 1000W; Protection Grade: IP55 |
| Fire Protection System | S-type aerosol fire extinguisher + smoke sensor + temperature sensor; cabinet-level fire detection & suppression |
| Protection Function | Details |
|---|---|
| Electrical Protection | Charging overvoltage, discharging undervoltage, charge/discharge overcurrent, short circuit protection |
| Temperature Protection | Charge/discharge over-temperature, charge/discharge low-temperature protection |
| Other Protection | Cell voltage/temperature difference protection, low insulation resistance protection, contactor adhesion protection, pre-charging failure protection |
IEC62619, CE, UN38.3
A: The series has four standard models: ICHES-30 (30kWh), ICHES-40 (40kWh), ICHES-50 (50kWh), ICHES-60 (60kWh). It supports up to 4 cluster cabinets in parallel, with the maximum expandable capacity of 240kWh (60kWh*4).
A: The system has an IP55 dustproof and waterproof protection grade, specially designed for outdoor/semi-outdoor installation and can adapt to various harsh on-site environments without additional protective buildings.
A: It is equipped with an integrated industrial-grade air-conditioning with 220Vac rated voltage, 2000W cooling capacity and 1000W heating capacity, which precisely controls the internal temperature of the cabinet.
A: The system is equipped with a cabinet-level intelligent fire protection system, including S-type aerosol fire extinguishers, smoke sensors and temperature sensors for real-time fire detection and rapid initial suppression.
A: The cycle life is 6000 cycles (25℃, 0.5C/0.5C, 90%DOD, 70% residual capacity); the standard warranty is 5 years, extendable to 10 years.
A: Yes, it supports WIFI remote management. The WIFI name is the battery SN code, default password is jjwl123!@#; access 172.16.254.254 via browser (default account/password: admin/admin) for network configuration.
A: The system uses hoisting + floor fixing installation; base bearing capacity >2000Kg, base height >200mm, minimum gap on sides/top ≥300mm/500mm; requires flat, dry ground without water accumulation.
A: Multi-dimensional safety protection including charging overvoltage/discharging undervoltage, charge/discharge overcurrent, short circuit, over-temperature/low-temperature, and other protection functions with fault self-diagnosis.
A: Standard communication protocol is CAN bus; compatible with mainstream energy storage inverters, with optional matching inverter for one-stop deployment.
A: Charging temperature range: 0℃ ~ 50℃, discharging temperature range: -20℃ ~ 55℃, recommended storage temperature: 20℃ ~ 30℃.