IG55 Clean Agent Suppression System, For Industrial
Description:
When a fire is detected, the IG55 system releases the inert gas mixture into the protected space. The gases quickly disperse, reducing the oxygen concentration to a level where the fire cannot sustain itself. The process is fast, efficient, and leaves no residue, ensuring minimal downtime and no secondary damage.
The IG55 fire extinguishing system is a reliable, sustainable, and effective solution for protecting critical infrastructure and assets from fire hazards. Its unique properties make it a preferred choice for industries where safety, environmental impact, and asset protection are paramount.
Technical parameters of IG55 fire suppression system
Working temperature (℃) | 0℃~+50℃ | ||
Working pressure | Storage pressure | 20.0MPa | 30.0MPa |
Max. working pressure (+50℃) | 23.2MPa | 36.6MPa | |
Min. working pressure (-20℃) | 18MPa | 27MPa | |
Container volume (L) | 80L | 140L | |
Filling weight (kg, @200 bar) | 22.32kg | 39.06kg | |
Filling weight (kg, @300 bar) | 33.48 kg | 58.59kg | |
System operating voltage | 220V AC,24V DC | ||
System start mode | Electrical automatic, electrical manual, mechanical emergency start | ||
Design concentration | Class A dangerous material surface fire | 40.3% | |
Class B | 47.6% | ||
The design concentration of the protective zone with people working | 40.3%~43% |
1 | Agent storage cylinder | 5 | Container valve | 9 | Manifold | 13 | Container valve for driving cylinder | 17 | Select valve |
2 | Frame | 6 | Flexible hose | 10 | Reducing devise | 14 | Solenoid actuator | 18 | Pressure switch |
3 | Cylinder clamp | 7 | Safety valve | 11 | Pilot tube | 15 | Relief valve | 19 | Nozzle |
4 | Gas driving actuator | 8 | Liquid flow check valve | 12 | Driving cylinder | 16 | Gas flow check valve |
| |
-- Clean and Non-Residu
-- Environmentally Friendly
-- Safe for Occupants
-- Effective Fire Suppression
-- Non-Conductive
- Telecommunications and data processing
- Switch gear rooms
- Military applications and cell sites
- High-tech medical application
- Computer rooms
- Telecommunication centers
- Records and data archives
- Testing/imaging equipment
- Reference material
- Chemical laboratories