3 Phase 3.6kV Vacuum Contactor - Medium Voltage Vacuum Contactor, rated voltage 3.6kV, rated current 800~2500A
General Description:
Hai Bang 3 Phase 3.6kV Vacuum Contactor – Type JCZ3-3.6D/D-800~2500A is suitable for AC 50~60Hz power systems, main circuit rated voltage 3.6kV, and rated current 800-3200A. The 3 Phase 3.6kV Vacuum Contactoris used to directly or remotely connect and disconnect the main circuit and frequently control AC motors, transformers and other electrical control occasions. Haibang 3 Phase 3.6kV Vacuum Contactor is widely used in petroleum, coal mine explosion-proof equipment and other occasions. The altitude of the environment where the 3.6kV 3 phase Vacuum Contactor is used does not exceed 1000 meters above sea level.
We have other types of 3 Phase 3.6kV Vacuum Contactors, whose rated current are 160A, 250A, 400A, 630A (JCZ3-3.6D/D-160~630A) and 3200A (JCZ3-3.6D/D-3200A). Please refer to the categories for more information.
Technical Data:
| Name | Unit | Value | ||||
| Main circuit | Rated working voltage (Ue) | kV | 3.6kV | |||
| Rated working current (Ie) | A | 800A~2500A | ||||
| Rated frequency (fr) | Hz | 50~60 | ||||
| Rated connecting capacity | kA | 12.5 | ||||
| Rated breaking capacity | kA | 10 | ||||
| Ultimate breaking capacity | kA | 12.5 | ||||
| Rated short time withstand current | kA | 10 | ||||
| Rated peak withstand current | kA | 12.5 | ||||
| Rated short circuit duration | s | 4 | ||||
| Power frequency withstand voltage | Wiring terminal to earth | kV | 18 | |||
| Vacuum breaks | kV | 18 | ||||
| Lightening impulse withstand voltage | kV | 40 | ||||
| Control circuit | Rated voltage (Us) | V | AC 110/220/380 | |||
| DC 110/220 | ||||||
| Rated power (Ps) electric holding(800~3200A) | VA | ≤600/50 (absorbing/holding) | ||||
| Rated power (Ps) mechanical holding(800~2500) | VA | ≤900/600 (Closing/opening) | ||||
| Auxiliary circuit | Form | (3a+2b) | ||||
| Rated value | AC 380V/5A, | |||||
| DC 380V/1A | ||||||
| Control circuit, auxiliary circuit to earth power frequency withstand voltage | kV | 2 | ||||
| Rated operating frequency | Long-term | time/h | 300 | |||
| Short-term | time/h | 600 | ||||
| Mechanical endurance | 10000 times | 10 | ||||
| Electrical endurance | 10000 times | 10 | ||||
| Mechanical characteristics | Closing time | ms | ≤200 | |||
| 3-phase asynchronous time | ms | ≤3 | ||||
| Original opening time | ms | ≤150 | ||||
| Closing tripping | ms | ≤10 | ||||
|
Remark: 1. rated control voltage can be made according to customer’s requirements. 2. For the mechanical holding type, the locking device needs to be replaced every 100,000 times. |
||||||