QUINT-PS/1AC/24DC/40 - Power supply 2866789
Primary-switched power supply unit QUINT POWER, Screw connection, DIN rail mounting, SFB Technology (Selective Fuse Breaking), input: 1-phase, output: 24 V DC / 40 A
QUINT POWER power supplies with maximum functionality QUINT POWER circuit breakers magnetically and therefore quickly trip at six times the nominal current, for selective and therefore cost-effective system protection. The high level of system availability is additionally ensured, thanks to preventive function monitoring, as it reports critical operating states before errors occur. Reliable starting of heavy loads takes place via the static power reserve POWER BOOST. Thanks to the adjustable voltage, all ranges between 5 V DC ... 56 V DC are covered.
Nominal input voltage range
100 V AC ... 240 V AC
Input voltage range
85 V AC ... 264 V AC
Derating
< 100 V AC (1 %/V)
Input voltage range AC
85 V AC ... 264 V AC
Input voltage range DC
90 V DC ... 300 V DC (UL 508: ≤ 250 V DC)
Electric strength, max.
300 V AC
Voltage type of supply voltage
AC
Inrush current
< 15 A (typical)
Inrush current integral (I2t)
< 1.7 A2s
AC frequency range
45 Hz ... 65 Hz
Frequency range DC
0 Hz
Mains buffering time
> 35 ms (120 V AC)
> 35 ms (230 V AC)
Current consumption
8.8 A (120 V AC)
4.6 A (230 V AC)
9.5 A (110 V DC)
4.7 A (220 V DC)
Nominal power consumption
1157 VA
Protective circuit
Transient surge protection; Varistor, gas-filled surge arrester
Power factor (cos phi)
0.88
Typical response time
< 0.7 s
Input fuse
20 A (slow-blow, internal)
Permissible backup fuse
B16 B25 AC:
Permissible DC backup fuse
DC: Connect a suitable fuse upstream
Recommended breaker for input protection
16 A ... 20 A (AC: Characteristics B, C, D, K)
Discharge current to PE
< 3.5 mA
DC operation
Nominal input voltage range
120 V DC ... 300 V DC (UL 508: ≤ 250 V DC)
Input voltage range
90 V DC ... 300 V DC (UL 508: ≤ 250 V DC)
Derating
< 120 V DC (0.5 %/V)
Voltage type of supply voltage
DC
Efficiency
> 92 % (for 230 V AC and nominal values)
Output characteristic
U/I
Nominal output voltage
24 V DC ±1 %
Setting range of the output voltage (USet)
18 V DC ... 29.5 V DC (> 24 V DC, constant capacity restricted)
Nominal output current (IN)
40 A (-25 °C ... 60 °C, UOUT = 24 V DC)
POWER BOOST (IBoost)
45 A (-25 °C ... 40 °C permanent, UOUT = 24 V DC )
Selective Fuse Breaking (ISFB)
215 A (12 ms)
Magnetic circuit breaker tripping
B2 / B4 / B6 / B10 / B16 / B25 / C2 / C4 / C6 / C13
Derating
60 °C ... 70 °C (2.5 %/K)
Feedback voltage resistance
≤ 35 V DC
Protection against overvoltage at the output (OVP)
≤ 35 V DC
Residual ripple
< 30 mVPP (with nominal values)
Short-circuit-proof
yes
Output power
960 W
Maximum no-load power dissipation
14 W
Power loss nominal load max.
80 W
Rise time
< 0.1 s (UOUT (10 % ... 90 %))
Connection in parallel
yes, for redundancy and increased capacity
Connection in series
yes
Signal: DC OK active
Output description
UOUT > 0.9 x UN: High signal
Switching voltage range
18 V DC ... 24 V DC
Output voltage
+ 24 V DC
Maximum inrush current
≤ 20 mA (short-circuit-proof)
Continuous load current
≤ 20 mA
Signal: DC OK floating
Output description
Relay contact, UOUT > 0.9 x UN: Contact closed
Maximum switching voltage
30 V AC
24 V DC
Maximum inrush current
0.5 A
1 A
Continuous load current
1 A
Signal: POWER BOOST, active
Output description
IOUT < IN: High signal
Switching voltage range
18 V DC ... 24 V DC
Output voltage
+ 24 V DC
Maximum inrush current
≤ 20 mA (short-circuit-proof)
Continuous load current
≤ 20 mA