Phoenix Contact QUINT4-PS/3AC/24DC/40/CO - Power supply 1783052
Primary-switched QUINT POWER power supply with free choice of output characteristic curve, SFB (selective fuse breaking) technology, and NFC interface, input: 3-phase, output: 24 V DC/40 A
The fourth generation of the high-performance QUINT POWER power supplies ensures superior system availability by means of new functions. Signaling thresholds and characteristic curves can be individually adjusted via the NFC interface. The unique SFB technology and preventive function monitoring of the QUINT POWER power supply increase the availability of your application.
Network type
Star network
Nominal input voltage range
3x 400 V AC ... 500 V AC
2x 400 V AC ... 500 V AC
Input voltage range
3x 400 V AC ... 500 V AC -20 % ... +10 %
2x 400 V AC ... 500 V AC -10 % ... +10 %
Typical national grid voltage
400 V AC
480 V AC
Voltage type of supply voltage
AC
Inrush current
typ. 1.5 A (at 25 °C)
Inrush current integral (I2t)
< 0.06 A2s
Inrush current limitation
1.5 A (after 1 ms)
AC frequency range
50 Hz ... 60 Hz -10 % ... +10 %
Frequency range (fN)
50 Hz ... 60 Hz -10 % ... +10 %
Mains buffering time
typ. 28 ms (3x 400 V AC)
typ. 28 ms (3x 480 V AC)
Current consumption
3x 1.8 A (400 V AC)
3x 1.5 A (480 V AC)
2x 3 A (400 V AC)
2x 2.5 A (480 V AC)
3x 1.5 A (500 V AC)
2x 2.4 A (500 V AC)
Nominal power consumption
1217 VA
Protective circuit
Transient surge protection; Varistor, gas-filled surge arrester
Power factor (cos phi)
0.95
Switch-on time
< 1 s
Typical response time
300 ms (from SLEEP MODE)
Recommended breaker for input protection
3x 4 A ... 20 A (Characteristic B, C, D, K or comparable)
Recommended fuse for input protection
≥ 300 V AC
Discharge current to PE
< 3.5 mA
1 mA (550 V AC, 60 Hz)
DC operation
Nominal input voltage range
± 260 V DC ... 300 V DC
Input voltage range
± 260 V DC ... 300 V DC -13 % ... +30 %
Voltage type of supply voltage
DC
Current consumption
2.2 A (±260 V DC)
1.9 A (±300 V DC)
Nominal power consumption
1217 VA
Recommended breaker for input protection
1x 6 A (10 x 38 mm, 30 kA L/R = 2 ms)
Recommended fuse for input protection
≥ 1000 V DC
Efficiency
typ. 95.7 % (400 V AC)
typ. 95.7 % (480 V AC)
Nominal output voltage
24 V DC
Setting range of the output voltage (USet)
24 V DC ... 29.5 V DC (constant capacity)
Nominal output current (IN)
40 A
Static Boost (IStat.Boost)
45 A
Dynamic Boost (IDyn.Boost)
60 A (5 s)
Selective Fuse Breaking (ISFB)
215 A (15 ms)
Magnetic circuit breaker tripping
A1...A40 / B2...B25 / C1...C13 / Z1...Z16
Derating
> 60 °C ... 70 °C (2.5 %/K)
Feedback voltage resistance
≤ 35 V DC
Protection against overvoltage at the output (OVP)
≤ 32 V DC
Control deviation
< 0.5 % (Static load change 10 % ... 90 %)
< 3 % (Dynamic load change 10 % ... 90 %, (10 Hz))
< 0.25 % (change in input voltage ±10 %)
Residual ripple
< 50 mVPP (with nominal values)
Short-circuit-proof
yes
No-load proof
yes
Output power
960 W
1080 W
1440 W
Maximum no-load power dissipation
< 5 W (400 V AC)
< 5 W (480 V AC)
Power loss nominal load max.
< 45 W (400 V AC)
< 45 W (480 V AC)
Power dissipation SLEEP MODE
< 2 W (400 V AC)
< 2 W (480 V AC)
Crest factor
typ. 1.6 (400 V AC)
typ. 1.9 (480 V AC)
Rise time
< 1 s (UOut = 10 % ... 90 %)
Connection in parallel
yes, for redundancy and increased capacity
Connection in series
yes
Fuse protection (secondary side)
electronic
thermal-magnetic
thermal
Input
Connection method
Screw connection
Conductor cross-section, rigid min.
0.2 mm²
Conductor cross-section, rigid max.
6 mm²
Conductor cross-section flexible min.
0.2 mm²
Conductor cross-section flexible max.
4 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, min.
0.25 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, max.
4 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, min.
0.25 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, max.
4 mm²
Conductor cross-section AWG min.
24
Conductor cross-section AWG max.
10
Stripping length
8 mm
Tightening torque, min
0.5 Nm
Tightening torque max
0.6 Nm
Output
Connection method
Screw connection
Conductor cross-section, rigid min.
0.5 mm²
Conductor cross-section, rigid max.
16 mm²
Conductor cross-section flexible min.
0.5 mm²
Conductor cross-section flexible max.
16 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, min.
0.5 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, max.
16 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, min.
0.5 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, max.
16 mm²
Conductor cross-section AWG min.
20
Conductor cross-section AWG max.
6
Stripping length
10 mm
Tightening torque, min
1.2 Nm
Tightening torque max
1.5 Nm
Number of phases
3
Insulation voltage input/output
4 kV AC (type test)
2.4 kV AC (routine test)
Insulation voltage output / PE
0.5 kV DC (type test)
0.5 kV DC (routine test)
Insulation voltage input / PE
3.5 kV AC (type test)
2.4 kV AC (routine test)
Switching frequency
32.00 kHz ... 100.00 kHz (Auxiliary converter stage)
55.00 kHz ... 300.00 kHz (Main converter stage)
25.00 kHz ... 500.00 kHz (PFC stage)