| Type | P400C860 | P500C1075 | P600C1290 | P700C1505 | P800C1720 |
|---|---|---|---|---|---|
| DC side parameters | |||||
| Cell type &capacity | LiFePO₄-280Ah | ||||
| Battery module type | 1P20S | ||||
| System configuration | 4*1P240S | 5*1P240S | 6*1P240S | 7*1P240S | 8*1P240S |
| Capacity(BOL) | 860kWh | 1075kWh | 1290kWh | 1505kWh | 1720kWh |
| AC side parameters | |||||
| Grid type | 3P4W+PE | ||||
| Rated output power | 400kW | 500kW | 600kW | 700kW | 800kW |
| Rated voltage | AC400V | ||||
| Rated frequency | 50/60(±5)Hz | ||||
| Maximum output current | 577A | 722A | 866A | 1010A | 1155A |
| Harmonics | <3%(@rated power) | ||||
| Overload capacity | 110%,10mins;120%,60s | ||||
| General parameters | |||||
| Isolation transformer | No | ||||
| Protection level | Outdoor installation (Battery cabinet:IP55,Electrical room:IP34) | ||||
| Container anti-corrosion grade | C3 | ||||
| Operation temperature* | -20℃~50℃ | ||||
| Relative humidity | 0~95%(non-condensing) | ||||
| Permissible altitude** | <2000m | ||||
| Cooling method | Battery cabinet:HVAC,Electrical room:forced air cooling | ||||
| Fire fighting system | FAS &FM200/Novec1230 | ||||
| Noise emission | ≤75dB | ||||
| Dimension (W*D*H) | 20HQ container (6058mm*2438mm*2896mm) | ||||
| Maximum weight | 24500kg | ||||
| Communication interface | Ethernet | ||||
| Communication protocol | Modbus TCP/IP | ||||
| Warranty | 5 years (can be extended to 10 years)Warranty | ||||
| Certification | System:UN3536,LVD,EMC,RoHS Cell:IEC62619,UL1973,UL9540A PACK:UN38.3 PCS:G99,EN50549,AS4777.2,VDE4105 | ||||

Q1: Is the system resistant to typhoons and heavy rainfall?
A: IP55 protection and robust container design withstand harsh weather. Anchoring kits are recommended for high-wind zones.
Q2: How does it handle high humidity and salt air?
A: C3 anti-corrosion and IP55 ensure durability in coastal and humid environments.
Q3: Can it operate during frequent power outages?
A: Yes. <200ms response time ensures quick backup power transition.
Q4: Is it compatible with local diesel generators?
A: Yes. Supports multiple energy inputs, including diesel gensets for hybrid setups.
Q5: What certifications apply?
A: UN3536, IEC62619, UL1973 ensure safe transport and operation under international standards.
Q1: Can EnerCube3.0 operate in extreme continental climates (-30°C winters)?
A: Operating range starts at -20°C. For colder areas, optional heating systems can be integrated.
Q2: How does it handle dusty, dry conditions?
A: IP55 rating protects against dust, and C3 anti-corrosion is suitable for dry environments.
Q3: Is it suitable for remote, off-grid mining sites?
A: Yes. Plug-and-play design reduces installation time, and remote monitoring minimizes onsite visits.
Q4: Can it integrate with wind power in windy regions?
A: Yes. Supports wind turbine integration via AC coupling.
Q5: What is the warranty for harsh environments?
A: 5-year warranty, extendable to 10 years, covering performance in demanding conditions.
Q1: How does EnerCube3.0 perform in desert heat above 45°C?
A: Rated for 50°C, with derating above 45°C. Advanced cooling maintains safety and efficiency.
Q2: Is it resistant to sand and dust storms?
A: IP55 battery cabinet provides excellent sand and dust ingress protection.
Q3: Does it meet UAE grid standards?
A: The PCS can be configured to local grid codes, with certifications including G99 and EN50549.
Q4: Can it be used for peak shaving in commercial buildings?
A: Yes. 400–800kW output range and fast response make it ideal for demand management.
Q5: How is fire safety ensured in high temperatures?
A: Automatic fire suppression (FM200/Novec1230) activates upon detection, preventing thermal runaway.